Cart
product added to request
XR-4x0 | XR-4x1 configure
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose :
- ltdata.Aluminiumdose :
- ltdata.Polyethylenanschlusskopf :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- ltdata.BetriebstemperaturPP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!