EF2X

Double pipe and filling pipe monitoring

Features

WHG

product family

level measurement

product class

overfill protection and leackage detector

suitable for

fluids

measurement principle

conductive


Special characteristics

  • with general technical approval for construction Z-65.13-405

  • Electronics integrated in the probe

  • High chemical resistance

Description

EF2L and EF2T -conductive- with general technical approval for construction Z-65.13-405

Technical Data

Properties
ltdata.Elektr.Anschluss
Stecker GDM
Protection class EN60529
IP 65 mit Dichtung
connection
PVC Überwurfmutter G 1 ¼“
ltdata.BetriebstemperaturPVC
max. +60 °C
ltdata.BetriebstemperaturPE
max. +80 °C
Storage temperature
-30...+85 °C
Operating pressure
max. 6 bar
Material
Pipe
PVC | PE
Sensor rods
Edelstahl 1.4571 | Hastelloy B/C | Titan | Tantal
tdata.ElektronikteilET-473L|ET-473T
nominal voltage
20...30 V DC
Power consumption
1 VA
Output contact
Schließer | Öffnerkontakt (NO/NC) (nicht potentialfrei)
Switching voltage
12...30 V DC
Switching current
max. 300 mA
Switching capacity
max. 9 W
Sensitivity range
2...30 kOhm
ltdata.

EF2X application-specific configuration

EF2 - [ 1 ] - [ 2 ] - [ 3 ] - [ 4 ] - [ 5 ]


1 Typ

  • L : Leckageüberwachung Doppelrohr
  • T : Trockenlaufschutz Befüllleitung

2 Anschluss

  • 00 : PVC-Überwurfmutter G 1 ¼”

3 Rohrmaterial und Anschlußkopf

  • PV : PVC
  • PE : Polyethylen

4 Stabmaterial

  • VA : Edelstahl 1.4571
  • HB : Hastelloy B
  • HC : Hastelloy C
  • TI : Titan
  • TA : Tantal

5 Elektronikteil

  • ET473L : Leckageüberwachung Doppelrohr
  • ET473T : Trockenlaufschutz Befüllleitung

Further product information

The conductive probes EF2L and T with integrated electronics ET-473L and ET-473T are used to monitor double pipes and/or filling pipes. 

The probes are approved by the DiBt for water-polluting liquids.

The conductive electrode EF2L, with integrated electronics part ET-473L, sets off an alarm in the event of leaks in double-walled pipelines. The conductive electrode EF2T, with integrated electronics part ET-473T, sets off an alarm if air instead of medium is present in the filling pipe. The use of these devices is preferred for water-polluting  iquids that require DiBt test certification. The housing material consists of either PVC or PE.

The probe’s electrode tips are made of either stainless steel (1.4571), hastelloy B/C, titanium or tantalum 
depending on the medium.

The electronics part is integrated directly into the probe tube. An optional NC or NO contact (closer or opener) is present at the connector port. Various installation and attachment parts can be supplied for the installation / attachment of the devices.

  • Approved by DiBt according to WHG (Water Resources Act)
  • High chemical resistance
  • Electronics integrated in the probe
  • NO or NC output
  • Leakage / pipeline monitoring
  • Filling pipe monitoring to 
  • protect against pressure surges
  • Available as a complete unit with bonding sleeves, welding sleeves and ball valve

The double pipe and filling pipe moni-toring EF2L and T can be connected to our “optical and acoustic alarm” series OAA-300.

Documents and Downloads

Accessoires

Our application engineers advise you personally, comprehensively and professionally!

Simply contact us by phone or e-mail!

Call us right away!

+49-6251-8462-0

contact form

Logo of Fluid.iO Sensor + Control

Fluid.iO
Sensor + Control
GmbH & Co. KG

An der Hartbrücke 6
64625 Bensheim
Tel.: +49-6251-8462-0
E-Mail: info@fluidio.de