Cart
product added to request
ES-Serie configure
EF 3…5 24 V configure
Ex-BK configure
Fluidix Lub-VDT configure
ES-Serie
electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
- Housing : Aluminium
- Protection class : IP30
- Dimensions : 197 x 153 x 37,5mm (B x H x T)
- Temperature range : 0 – 50°C
- Supply voltage : 24V DC +/-20%
- Power consumption : 120mA – 220mA
- Reverse polarity protection : ✓
- Display : 4x20
Outputs
- analog 0(4)–20mA : 3x
- digital : 4x
- fixed for alarm : 1x
- free configurable : 3x
display of measured value
- Flow velocity :
- Filling level :
- flow :
- flow rate :
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- connection : integrierter Anschlusskopf
- Protection class : IP 65
- connection thread : G 1¼"
- Material Screw connection : PPH
- Material electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- material coating : PTFE
- Coating length : voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
- Rod diameter : 4 mm, 6 mm
- rod length : max. 6 m
- Operating temperature : 85 °C
- Operating pressure : atmosphärisch
- Spacer : ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24 V DC ± 15%
- Power consumption : max. 2 W (Klemme A1, A2)
- Switching voltage : max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
- Switching current : max. 3 A AC, 3 A DC min. 1 mA
- Switching capacity : max. 750 VA, 150 W
- Sensitivity : 3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –20...+120 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
- Dimensions : 80 mm x 75 mm x 57 mm
Material
- Housing : Aluminium
- Mounting clip : V2A
- Rivet : V2A
- Screw connection : M 20 x 1.5, V2A
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 24...250 V AC/DC
- Switching current : 20 mA...6 A AC/DC
- Switching capacity(min.) : max. 500 VA, 60 W
- Switching capacity(max.) : min. 2 VA/W
Fluidix Lub-VDT
Oil condition sensor for permanent monitoring of mechanical properties of liquids
The FluidIX Lub-VDT enables inline monitoring of mechanical fluid properties.
Properties
- CE marking : EN 61000-6-1/2/3/4
- Operating voltage : 9...32 V DC
- Housing material : Edelstahl
- Protection class : IP 67
- Dimensions : 30x90 mm
- Process connection : G 3/8"
- Electrical connection : M12-8 A-Coding
- Weight : 150g
- Measurement output : 2x 4...20mA
- bus protocol : ModbusRTU, CANopen
Measured variables
- Resonator frequency : 20...25 kHz
- Viscosity : 1-650 cSt (mm²/s)
- density : 0.5-1.5 g/cm³
- Temperature : -40...+125°C
- sampling rate : 1/s
Operating conditions
- Temperature of the fluid : -40...+125°C
- Housing temperature : -40...+100°C
- oil pressure : Max. 50 bar
- particle size : 250 μm
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
Our application engineers advise you personally, comprehensively and professionally!