KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties KS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…10% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- Weight : ca. 150g
- ltdata. :
Power supply
- nominal voltage : siehe Typenschlüssel
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
- Switching delay : siehe Typenschlüssel
- Sensitivity range : siehe Typenschlüssel
Output
- Contacts : potentialfreie Wechselkontakte
- Switching voltage(min) : 5 V
- Switching voltage (max) : 250 V AC / 150 V DC
- Overvoltage category : EN 61010-1 Kategorie III
Switching current
- Switching current : min. 5 mA
- Switching current : max. cos φ =1 5 A
- Switching current : max. cos φ = 0,7 3 A/AC
- Switching current : max. cos φ = 1
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (oponal)
- Overpressure : 1,2* (1,5*) x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
- Pressure range : 5…1.000 bar
Operating conditions
- Operating voltage : 14...28 VDC ± 10 %
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : G1/4" (andere auf Anfrage)
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Weight : ca. 170g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
KS-410 KS-420
Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
properties KG-410
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
properties KG-420
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
- Dimensions (LxBxH in mm) : 30 x 45,4 x 97,3
- Protection type/class : Gehäuse IP66, Stecker IP 67
- Weight : 96g
Measuring range
- measuring range (Humidity) : 0…10% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
Our application engineers advise you personally, comprehensively and professionally!