Stainless steel ball 61 mm Ø
:
max. 20 bar | 0,65 g/cm³
Stainless steel cylinder 44 mm Ø
:
max. 15 bar | 0,76 g/cm³
min. contact gap type 03
:
75 mm
min. contact gap type 04
:
85 mm
min. contact gap type 09
:
75 mm
Switching contacts and switching capacity
Changeover contact
:
max. 3x | 60W/VA
normally open
:
max. 5x | 100 W / VA
Normally closed contact
:
max. 3x | 60 W/VA
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
11,12, 15, 17
connection cable
:
1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating pressure
:
max. 6 bar
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
Operating temperature
PVC
:
max. 60 °C
PE
:
max. 80 °C
PP
:
max. 90 °C
MaterialDensity
Type 11
:
0,60 g/cm³
Type 12
:
1,00 g/cm³
Type 15
:
0,59 g/cm³
Type 17
:
0,63 g/cm³
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Protection class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Properties TPS-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (dew point)
:
-50…+80 °C
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
connection
:
G 1” (andere Gewinde auf Anfrage)
max.length guide tube
:
siehe Diagramm
Operating temperature
:
atmosphär. Bedingungen
Operating pressure
:
atmosphär. Bedingungen
media density
:
siehe Eintauchtiefe
Number of contacts
:
beliebig
Contact load
:
max. 10 VA, max. 230 V AC
Length
:
max. 1750 mm
Material
Sight tube
:
PVC transparent
connection
:
PVC-Verschraubung mit PTFE-Stangenführung
Guide rod
:
Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
float
:
PE / PP
Our application engineers advise you
personally, comprehensively and professionally!