Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
Material
:
1.4571 / 1.4404 (316Ti / 316L)
Protection class
:
IP65
Process temperature
:
-10°C … +130°C | (integriertes Pt100 im Messfühler)
max. process pressure
:
Vakuum ... 64 bar
Process connections
:
NPT | M48 | Varivent® | Tri-Clamp
Cable length sensor - transmitter
:
Max. 1.000 Meter
max. flow velocity
:
5 m / sec
Ex approval
:
II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
Sphere
:
VA-100B
Cylinder
:
VA-100C
Repeatability
VA-100B
:
± 0,5% | ± 1 Digit
VA-100C
:
± 0,3% | ±1 Digit
Measuring ranges
VA-100B
:
0,1 - 2.500 mPa·s x g/cm³
VA-100C
:
10 - 25.000 mPa·s x g/cm³
Probe dimensions
VA-100B
:
Ø 32 x 145 mm
VA-100C
:
Ø 32 x 120 mm
installation positions
Reservoir
:
tanks
:
Pipe
:
flow cell
:
Installation is position-independent
:
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Box
:
Polyethylen-Anschlusskopf (PE)
Cable
:
Kabel (TPK)
Plug
:
Stecker (ST)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
Measuring range
:
-40…+80 °C
deviation
:
± 0,3 K (10...80 °C)
Measuring element
:
Halbleiter-Diodenfühler
measuring resolution
:
0,1 K
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Operating voltage
:
10...48 V
Operating conditions
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Shock resistance
:
30g, Dauer: 14 ms bei Raumtemperatur
Vibration resistance
:
10g bei 20 bis 1000 Hz
Minimumairspeedrequiredformeasurementacrossthesensor
:
1,5 m/s
ZS-Serie
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
Pressure type
:
Differenzdruck
Housing
:
Aluminium
medium
:
Luft und nicht aggressive Gase
Measurement parameters
response time
:
< 2,5 s
Hysteresis
:
0,1 %
Overload capacity
:
4* fach bis 500 mbar, darüber 2* fach
Signal output selection
:
0...10 V | 4...20 mA, 2-Leiter