Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
Connection aluminium box
:
H30 x B50 x T45 mm
Connection polyester box
:
H56 x B80 x T75 mm
connection cable
:
1000 mm PUR blau
Protection class Socket
:
IP65
Material Sliding tube
:
VA 1.4571
Material of the angle fastening
:
VA 1.4408
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm
Mounting
:
2 Schlauchschellen
Accessories
:
R/I-Wandler TK-101
QFSK-2X
Stainless steel float switch combination
Float switch combinations QFSK for level monitoring & level control with maximum and minimum contact sensor.
Properties
Protection class EN60529
:
IP 68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
rod length
:
max. 5 m
Number of floats
:
bis 5
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Ex-protection
:
optional; IBExU10ATEX 1089
Operating pressure WFSK-25
:
max. 15 bar
Operating pressure QFSK-26
:
max. 6 bar
QFS-1X
Float switch with reed switch (mercury-free)
Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Properties
Protection class EN60529
:
IP 68
Cable entry
:
PVC , PTFE
Conductor cross-section
:
3 x 0,75 mm², PUR 3x0,5mm²
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC (QFS-11 nur NO oder NC)
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Float
Material Float
:
PE (Polyethylen)
ltdata.
:
ltdata.
:
ltdata.
:
Operating temperature
TPK(V), AEM
:
max. + 60 °C
PUR
:
max. + 70 °C
Silicone,Tefloncable with PE float
:
max. + 80 °C
Operating pressure
Cylinder
:
max. 1 bar
Sphere
:
max. 2 bar
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
Weight
:
ca. 150g
ltdata.
:
Power supply
nominal voltage
:
siehe Typenschlüssel
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Switching delay
:
siehe Typenschlüssel
Sensitivity range
:
siehe Typenschlüssel
Output
Contacts
:
potentialfreie Wechselkontakte
Switching voltage(min)
:
5 V
Switching voltage (max)
:
250 V AC / 150 V DC
Overvoltage category
:
EN 61010-1 Kategorie III
Switching current
Switching current
:
min. 5 mA
Switching current
:
max. cos φ =1 5 A
Switching current
:
max. cos φ = 0,7 3 A/AC
Switching current
:
max. cos φ = 1
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Protection class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Properties TPS-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (dew point)
:
-50…+80 °C
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
PPS-390
PPH float with magnet insert
for actuating monostable and bistable contacts
Variants
32
:
AußenØ 26 x 180 mm, für RohraußenØ 32 u. 34 mm Gewicht ca. 38 g
37
:
AußenØ 29,5 x 170 mm, für RohraußenØ 40 mm (PN 16) Gewicht ca. 62 g
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
Our application engineers advise you