The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties TPS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…100% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-50...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
Dimensions
:
180 x 48 x 36,5 mm ( L x B x H )
Weight
:
ca. 1,5 kg
Protection class
:
IP68
Cable length (standard)
:
15 m
Bending radius
:
> 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
Temperature range
:
0°C ... 50°C
Mounting shoe material
:
V2A 1,5mm
Certificates
EX / ATEX
:
IBExU 04 ATEX 1256
Measuring principle
Flow velocity: Ultrasonic Doppler
:
Filling level: Differential pressure
:
Flow velocity
Measuring range
:
0,01 - 4 m / s
Measuring accuracy
:
+/- 5 % vom Momentanwert im Kanal
Temperature drift
:
0,1% / °C ( Meßspanne )
Temperature drift
:
0,05% / °C ( Nullpunkt )
Output signal
:
4 - 20 mA
Filling level
Measuring ranges
:
0 –1 m ; 0 – 2 m ; 0 – 4 m
Measuring accuracy
:
< 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
Temperature drift
:
0,005% / °C v.E. Meßspanne
Temperature drift
:
0,005% / °C v.E. Nullpunkt
Material
:
Al2O3 (96%) aktive Fläche
Output signal
:
4 – 20 mA
Zero point
:
norm 4 mA ( +/- 3 % )
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
max. 60 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24…230 V AC/DC
Power consumption
:
≤ 2 W
Output
Output contact
:
2 potentialfreie Wechselkontakte
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 5 A AC / 5 A DC
Switching capacity
:
max. 750 VA / 90 W
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
CE marking
:
siehe Konformitätserklärung
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Our application engineers advise you
personally, comprehensively and professionally!