The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
LGW-13
CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Accuracy
:
+-3% vom Messbereich (30 ppm bei 3.000 ppm)
Relay output:
:
Potentialfrei
Response time
:
ca. 20 s
Operating voltage
:
24 V DC, 150 mA
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
2 Wechselkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ltdata.
:
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ