Cart
product added to request
OAA-300 configure
MTA configure
XR-6x0 | XR-6x1 configure
HE configure
XR-4x2 configure
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose :
- ltdata.Aluminiumdose :
- ltdata.Polyethylenanschlusskopf :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- ltdata.BetriebstemperaturPP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
- Temperature: : -40...80°C
- rel. Humidity : 0 - 100% rH
Measuring range
- measuring range (dew point) : -50...+80°C
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V oder 4...20mA
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : – 20…+60 °C
- Storage temperature : – 30…+80 °C
- Sensitivity : bei konduktiver Messung: 3, 10, 30, 100kΩ
- Dimensions : 170 x 190 x 85 mm
- Weight : ca. 0,8 kg
Control circuits
- Open circuit voltage : max. 10 V DC
- Short-circuit current : max. 10 mA
- Switching delay : ca. 0,5 s
Power supply
- nominal voltage : 230 V AC (optional 24, 115, 240 V AC 24 V DC
- Nominal frequency : 48...62 Hz
- Power consumption : max. 3 W/VA
Output
- Switching voltage : max. 250 V
- Switching current : max. 3 A
- Switching capacity : max. 500 VA | max. 50 W
- Volume : 75 dB
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
- Tank connection : Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
- Material : siehe Maßbild
- Material Tube : PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
- Operating temperature : –20...+60 °C
- Operating pressure : atmosphärisch
Material Float
- PPH : Ø 70 mm 460 g
- PVC : Ø 70 mm 455 g
- PPH : Ø 40 mm 370g
- PE : Ø 70 mm ca. 450 g
Material Rope
- PPH : (rot, Ø 2 mm) ~ 2 g/m
- Polyester : (bunt, Ø 2 mm) ~ 4 g/m
- PTFE : (weiss, Ø 3 mm) ~ 10 g/m
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
- Quiescent current : umschaltbar
HE
Pendant electrodes – single, multiple
suitable for high tanks, wells and sewers
tdata.AnschlussmitDose
- Protection class EN60529 : IP 54
- connection thread : G 2”
tdata.AnschlussohneDose
- Protection class EN60529 : IP 67
- connection thread : n.a. / G 2”
Material
- electrode body : PVC, PTFE, PPH
- Screw connection : PVC, PTFE
- Cable : PVC, PTFE
- electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
Operating temperature
- ltdata.HE-PVC : 60 °C
- ltdata.HE-PTFE : 150°C
XR-4x2
Electrode relay with ATEX and WHG approval
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
T201
Immersible Magnetic Probe made of stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
T201 PTFE
Immersible Magnetic Probe made of PTFE
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
Our application engineers advise you personally, comprehensively and professionally!