Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : PO-Dose oder AA-Dose
- Protection class : IP 65 Dose
- Float type : max. 6x Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- Number of contacts : max. 7x Wechsler / max. 10x Schließer / 7x Öffner
- Switching current : 1A, 2A
- Switching capacity : Wechsler 60W/VA | Schließer 100 W/VA | Öffner 60 W/VA
- min. contact distance with several floats : 125 mm
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾", S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal, Kohlestifte
- Operating temperature : PE, PVC: atmosphärisch PPH : 90 °C, PVDF: 100 °C
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ je nach Ausführung
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Technical specifications electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24...30 V DC
- Power consumption : max. 2 W
- Switching voltage : max. 230 V AC / V DC min. 5 V DC (CMOS-Relais)
- Switching current : max. 0,12 A AC / A DC min. <1 mA
- Switching capacity : max. 25 VA / W
- Sensitivity : 3k … 100 kΩ
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
- Housing : Robustes Aluminiumgehäuse
- Operating voltage : 18...36V DC (max. 400 mA @18V)
- Dimensions : 150 x 119 x 82 mm (L x B x H)
Operating conditions
- Operating temperature: : 0...+70 °C (optional 0...+90 °C)
- Maximum operating pressure: : 10 bar (optional 30 bar)
- Storage temperature: : -40...+90 °C
Connection
- ModBus TCP/IP : Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
- Digital I/O ports : 1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
- User Interface : grafisch über Weboberfläche im eingebundenen Netzwerk
TK-307
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Connection housing : Aluminium H 30 mm x B 50 mm x T 45 mm
- Connection socket : Polyester H 55 mm x B 80 mm x T 45 mm
- Protection class socket / plug : IP 65
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution depending on type : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
T200
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7