Robust sulphur hexafluoride sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-203e-IR is an SF6 sensor for measuring sulphur hexafluoride concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x15
Measuring ranges
in ppm
:
in vol%
0...1.000ppm
:
0...0,1 vol%
0...2.000ppm
:
0...0,2 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff mit LCD-Anzeige (oponal)
Overpressure
:
1,2* (1,5*) x Nenndruck
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Signal output selection
:
0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
Pressure range
:
5…1.000 bar
Operating conditions
Operating voltage
:
14...28 VDC ± 10 %
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
Connections
Electrical connection
:
Schraubklemme im Gehäuse
Process connection
:
G1/4" (andere auf Anfrage)
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W