The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
EFV2 20…230V
Conductive electrodes with 24...230 V direct connection
The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
T209
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
ZT-H
High pressure sensor for liquid and gaseous media
Versatile use in industrial applications for measuring ranges up to 4,000bar
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
Temperature:
:
-40...80°C
rel. Humidity
:
0 - 100% rH
Measuring range
measuring range (dew point)
:
-50...+80°C
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V oder 4...20mA
BI
Bistable Switch
Properties
Protection class
:
IP 65
Switching current
:
max. 1 A
Switching voltage
:
max. 24 V
Switching capacity
:
max. 20 W/VA
Material
Housing
:
Messingrohr Ø 10 x 1
Cable
:
TPK (PVC basis) | SIL (Silikon)
Operating temperature
TPK
:
–15 ° ... + 60 °C
SIL
:
–15 ° ... +130 °C
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
Operating voltage
:
12...32 V DC (max. 0,2 W)
Dimensions
:
Ø 22 x 59 (D x H), SW22
Housing
:
Edelstahl
ltdata.MessbereichNenndruck
:
-1…500 bar
Overpressure
:
2 x Nenndruck
Bursting pressure
:
4 x Nenndruck
Protection class
:
IP65
Output signal
:
ZILA-DIO
Operating conditions
Pressure type
:
Relativdruck
Temperature of the fluid
:
-40 …+125 °C
ltdata.Medientemperatur(optional)
:
-20 …+125 °C
Ambient temperature
:
-40 …+105 °C
electrical connection
ltdata.Standard
:
Binder M12 x 1
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
Our application engineers advise you
personally, comprehensively and professionally!