Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
connection
:
integrierter Anschlusskopf
Protection class
:
IP 65
connection thread
:
G 1¼"
Material Screw connection
:
PPH
Material electrode rods
:
Edelstahl (1.4571), Hastelloy C, Titan, Tantal
material coating
:
PTFE
Coating length
:
voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
Rod diameter
:
4 mm, 6 mm
rod length
:
max. 6 m
Operating temperature
:
85 °C
Operating pressure
:
atmosphärisch
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
Operating temperature
:
–20...+85 °C
Storage temperature
:
–30...+85 °C
nominal voltage
:
24 V DC ± 15%
Power consumption
:
max. 2 W (Klemme A1, A2)
Switching voltage
:
max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
Switching current
:
max. 3 A AC, 3 A DC min. 1 mA
Switching capacity
:
max. 750 VA, 150 W
Sensitivity
:
3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
LGW-13
CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
: