Immersible Magnetic Probe made of stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
Lub-VDT USB-Kit
Software and USB kit for configuration & evaluation
Properties
details
:
folgen
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
2 Wechselkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ltdata.
:
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
Housing
:
Aluminium
Protection class
:
IP30
Dimensions
:
197 x 153 x 37,5mm (B x H x T)
Temperature range
:
0 – 50°C
Supply voltage
:
24V DC +/-20%
Power consumption
:
120mA – 220mA
Reverse polarity protection
:
✓
Display
:
4x20
Outputs
analog 0(4)–20mA
:
3x
digital
:
4x
fixed for alarm
:
1x
free configurable
:
3x
display of measured value
Flow velocity
:
Filling level
:
flow
:
flow rate
:
Our application engineers advise you
personally, comprehensively and professionally!