Cart
product added to request
QFS-3X configure
TK-303 configure
EE-2X configure
QFS-3X
Mercury-free float switch with µ-switch
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE bzw. PVDF
- Conductor cross-section : 3 x 0,75 mm², PUR 3x 0,5mm²
- Operating pressure cylinder : max. 1 bar
- Operating pressure sphere : max. 2 bar
- Switching system : µ-Schalter
- Contact : Wechsler, NO, NC
Material Float
- QFS-30 : PPH (Polypropylen)
- QFS-31 : PPH (Polypropylen)
- QFS-34 : PE (Polyethylen)
Cable
- TPK : PVC Basis Ø 5,9 mm
- TPKV : PVC verstärkt Ø 7,3 mm
- PUR : Polyurethan Ø 5,4 mm
- SIL : Silikon Ø 6,4 mm
- FEP : Teflon Ø 4,0 mm
- AEM : Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
- TPK : 70 mm
- TPKV : 90mm
- PUR : 100mm
- SIL : 80 mm
- FEP : 110 mm
- AEM : abhängig vom Innenkabel
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
- Silicone, Teflon cable with PP float : max. + 85 °C
MaterialDensity
- QFS-31 : ≥≥ 0,6 g/cm³
- QFS-34 : ≥≥ 0,75 g/cm³
- QFS-30 TPK(V) cable : ≥≥ 0,85 g/vcm³
- QFS-30 PUR cable : ≥≥ 0,95 g/cm³
- QFS-30 SIL cable : ≥≥ 0,90 g/cm³
- QFS-30 FEP cable : ≥≥ 0,95 g/cm³
- QFS-30AEM cable : ≥≥ 0,90 g/cm³
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
EE-2X
electrode, multiple for Ex-Zone 0 (Cat. 1)
The conductive electrodes of the EE-21/EE-22 series enable the monitoring of conductive liquids within the Ex area Zone 0 (Cat. 1).
Variants
- cable connection on side : EE-21
- cable connection on top : EE-22
Properties
- connection : Edelstahl (1.4571)
- Protection class EN60529 : IP65
- Ex-protection : TÜV 02 ATEX 1796 X
- Ex protection type : II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
- connection thread : G1" | G1¼"
- Cable entry EE-21 : Edelstahl (1.4571)
- Cable entry EE-22 : Kunststoff
- Rod diameter : 4 mm | 6 mm
- rod length : max. 6.000 mm
- Operating pressure media side : max. 40 bar
- Spacer : ab Länge > 1000 mm je 1 pro 1000 mm
Material
- electrode body : Edelstahl (1.4571)
- Seal (head) : Viton
- Seal (media side) : Viton | PTFE
- Potential equalisation conductor connection : Edelstahl (1.4571)
- electrode rods : Edelstahl (1.4571) | Hastelloy C | Tantal
- Coating : PTFE
Operating temperature
- Category 1 Class T6...T1 : 60 °C
- Category 2 Class T6 : 80 °C
- Category 2 Class T5 : 95 °C
- Category 2 Class T4 : 130 °C (100°C)
- Category 2 Class T3...T1 : 150 °C (100°C)
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!