Cart
product added to request
Get an offer
Your cart
EF2...5 configure
W-35X configure
TK-307-0 configure
BK-390 configure
ZMF-100-IR configure
ES-20 configure
ZS-2 configure
T-200.L Ex configure
QFS-40 configure
TK-101 EX configure
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
- Measuring range : -40…+80 °C
- deviation : ± 0,3 K (10...80 °C)
- Measuring element : Halbleiter-Diodenfühler
- measuring resolution : 0,1 K
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 10...48 V
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
- Minimumairspeedrequiredformeasurementacrossthesensor : 1,5 m/s
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
W-35X
Water Level Gauge with sight glass indicator
The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
- Tank connection : Flansch ab DN 25 oder Verschraubung ab G ½"
- Material Float : PPH max. 2,5 bar, Glas max. 10 bar
- cable length : bei monostabilem Kontakt: Standard 2 m
- Number of contacts : beliebig
- Contact distance : min. 10 mm
- Temperature of the fluid : mit Plexiglasrohr max. +70 °C
- media density : ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
- Material tube sight glass : transparentes PVC
- Temperature of the fluid : max. +60 °C
- Operating pressure : max. 2,5 bar
- Material flange : PVC
- Material connection with angle valve : PVC
- Material sealing ring : Gummi
Properties W-351
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Rotguss
- Material connection with angle valve : Rotguss
- Material sealing ring : Silikon
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-352
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4571 als Bogen 90°
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-353
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4401
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
- Connection aluminium box : H30 x B50 x T45 mm
- Connection polyester box : H56 x B80 x T75 mm
- connection cable : 1000 mm PUR blau
- Protection class Socket : IP65
- Material Sliding tube : VA 1.4571
- Material of the angle fastening : VA 1.4408
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
ES-20
Pressure limiter | Pressure monitor | Safety pressure limiter | Pressure regulator | electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
Connections
- Process connection Relative pressure : G 1/4 Innengewinde
- Process connection differential pressure : G 1/8 Innengewinde
- Analogue current output : 1 x 4...20 mA
- Digital inputs/outputs : Konfigurierbar als 2 x Alarm oder 1 x Alarm und 1 x Fernentriegelung
Measuring range relative pressure
- Nominal pressure : -1...500 bar variabel wählbar
- Overload pressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
Measuring range differential pressure
- Nominal pressure : 0...1 mbar 0...10 mbar 0...50 mbar 0...100 mbar 0...250 mbar 0...1.000 mbar
- Overload pressure : 10 x Nenndruck
- Bursting pressure : 15 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
ZS-2
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...2,5mbar :
- 0...5mbar :
- 0...10mbar :
- 0...25mbar :
- 0...50mbar :
- 0...100mbar :
- 0...250mbar :
- 0...500mbar :
- 0...1.000mbar :
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
T209-0
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : PO-Dose oder AA-Dose
- Protection class : IP 65 Dose
- Float type : max. 6x Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- Number of contacts : max. 7x Wechsler / max. 10x Schließer / 7x Öffner
- Switching current : 1A, 2A
- Switching capacity : Wechsler 60W/VA | Schließer 100 W/VA | Öffner 60 W/VA
- min. contact distance with several floats : 125 mm
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
- Switch housing : PPH| PVDF
- Seal : NBR (PPH) | FPM (PVDF)
- Operating temperature : PPH max. 80 °C| PVDF max. 100 °C
- Operating pressure : max. 10 bar
- Mounting position : horizontal (±30° von der Horizontalen)
- Contact assembly : Schliesser-, Öffnerkontakt (je nach Einbau)
- Electrical connection : PVC-Kabel
- Switching capacity : max. 230 V AC/DC| max. 40 VA, max. 2 A
- Contact resistance : max. 80 mW
- Min. electric strength : 400 V DC / 1 s
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- fluid density : PPH > 0,6 kg/dm³ | PVDF > 0,95 kg/dm³
- Protection class : IP 68
Connections
- external installation : G ½"
- internal installation : M16
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
Smart Pressostat App
App for control of ES-2X devices over Bluetooth
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
- platform : Android
- Android Version : 12
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!