Cart
TK-312 configure
QFS-12 configure
QFS-3X configure
EE-2XF configure
T-200.F Ex configure
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA, 2W
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0-4...10 kW
Output
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Current output : 0/4... 20 mA bezogen auf die Masse des Eingangs
- Voltage output : 0/2... 10 V
- Mounting : Tragschiene nach EN 50022
- Weight : 175 g
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
- Protection class EN60529 : IP68
- Side installation : PVC-Stopfbuchsverschraubung G 2”
- Installation from above : PVC-Stopfbuchsverschraubung G 2”
- Operating pressure : max. 2 bar
- Contact : Wechselkontakt
- Switching voltage : 4....250 V AC / DC
- Switching current : 1mA.....1A
- Switching capacity : 60W/VA
- media density : ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
- Material Float : Polyethylen
Cable
- TPK : PVC Basis
- TPKV : PVC Basis verstärkt
- PUR : Polyurethan
- NEO : Neopren
- SIL : Silikon
- FEP : Teflon
- AEM : Ethylen-Acrylat-Kautschuk
Operating temperature
- TPK(V), NEO, AEM : max.+60 °C
- PUR : max.+70 °C
- FEP, SIL : max.+80 °C
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
- Dimensions : 180 x 48 x 36,5 mm ( L x B x H )
- Weight : ca. 1,5 kg
- Protection class : IP68
- Cable length (standard) : 15 m
- Bending radius : > 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
- Temperature range : 0°C ... 50°C
- Mounting shoe material : V2A 1,5mm
Certificates
- EX / ATEX : IBExU 04 ATEX 1256
Measuring principle
- Flow velocity: Ultrasonic Doppler :
- Filling level: Differential pressure :
Flow velocity
- Measuring range : 0,01 - 4 m / s
- Measuring accuracy : +/- 5 % vom Momentanwert im Kanal
- Temperature drift : 0,1% / °C ( Meßspanne )
- Temperature drift : 0,05% / °C ( Nullpunkt )
- Output signal : 4 - 20 mA
Filling level
- Measuring ranges : 0 –1 m ; 0 – 2 m ; 0 – 4 m
- Measuring accuracy : < 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
- Temperature drift : 0,005% / °C v.E. Meßspanne
- Temperature drift : 0,005% / °C v.E. Nullpunkt
- Material : Al2O3 (96%) aktive Fläche
- Output signal : 4 – 20 mA
- Zero point : norm 4 mA ( +/- 3 % )
QFS-3X
Mercury-free float switch with µ-switch
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE bzw. PVDF
- Conductor cross-section : 3 x 0,75 mm², PUR 3x 0,5mm²
- Operating pressure cylinder : max. 1 bar
- Operating pressure sphere : max. 2 bar
- Switching system : µ-Schalter
- Contact : Wechsler, NO, NC
Material Float
- QFS-30 : PPH (Polypropylen)
- QFS-31 : PPH (Polypropylen)
- QFS-34 : PE (Polyethylen)
Cable
- TPK : PVC Basis Ø 5,9 mm
- TPKV : PVC verstärkt Ø 7,3 mm
- PUR : Polyurethan Ø 5,4 mm
- SIL : Silikon Ø 6,4 mm
- FEP : Teflon Ø 4,0 mm
- AEM : Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
- TPK : 70 mm
- TPKV : 90mm
- PUR : 100mm
- SIL : 80 mm
- FEP : 110 mm
- AEM : abhängig vom Innenkabel
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
- Silicone, Teflon cable with PP float : max. + 85 °C
MaterialDensity
- QFS-31 : ≥≥ 0,6 g/cm³
- QFS-34 : ≥≥ 0,75 g/cm³
- QFS-30 TPK(V) cable : ≥≥ 0,85 g/vcm³
- QFS-30 PUR cable : ≥≥ 0,95 g/cm³
- QFS-30 SIL cable : ≥≥ 0,90 g/cm³
- QFS-30 FEP cable : ≥≥ 0,95 g/cm³
- QFS-30AEM cable : ≥≥ 0,90 g/cm³
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
- connection : Edelstahl (1.4571)
- Protection class : IP 65
- Ex-protection : TÜV 02 ATEX 1796 X
- Ex protection type : II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
- connection thread : G1", G1¼", G1½”
- Coating length : voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
- Rod diameter : 4 oder 6 mm
- rod length : max. 6 m
- Operating pressure media side : max. 40 bar
- Maximum permissible electrical connection values : Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
- Connection values : Ui 15V | Li 10 mA | Pi 100 mW
- Internal inductances / capacitances : vernachlässigbar klein
- Spacer : ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
- Category 1 Class T6...T1 : 60 °C
- Category 2 Class T6 : Medien & Umgebung 80 °C
- Category 2 Class T5 : Medien & Umgebung 95°C
- Category 2 Class T4 : Medien 130°C, Umgebung 100°C
- Category 2 Class T3...T1 : Medien 150°C, Umgebung 100 °C
Material
- Cable entry EE-21 : Edelstahl (1.4571)
- Cable entry EE-22 : PVDF
- Electrode body material : Edelstahl (1.4571)
- Seal (head) : Viton
- Seal (media side) : Viton / PTFE
- Potential equalisation conductor connection : Edelstahl (1.4571)
- Material electrode rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Tantal
- material coating : PTFE
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Ex-Polyester
- Box : Ex-Aluminium
Properties
- Protection class EN60529 : IP 65
- connection thread : G2"
- Union nut : G 2¾"
- Guide tube length : max. 6 m
- Operating temperature : -20…+60 °C
- Operating pressure : max. 6 bar je nach Ausführung
- media density : ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- Ex-protection : siehe Baumusterprüfbescheinigung
- CE marking : siehe Konformitätserklärung
CS-11
CO2 Sensor with digital Interface
Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
- Measured variable: : CO2
- Measuring range: : 0…5.000 ppm
- Measuring principle: : optisch, NDIR
- Housing : Kunststoff
- measuring grid : 2 sec.
- Accuracy : ± 50 ppm
- Protocol : I²C-Bus
- Operating conditions Temperature : -0°C … 50°C
- Operating conditions Humidity : 0…85 % rH
- Storage conditions Temperature : -30°C … 70 °C
- Storage conditions Humidity : 0…85 % rH
Properties MV-CAN
- Housing : Plastik
- Mounting : Hutschienenmodul für Einbau in Schaltschrank
- Operating voltage : 10…48 V
- measuring grid : 2 sec.
- CAN protocol : CANopen 2.0 A nach CiA DS 404
- Physical Layer : nach ISO 11898
- Option : Bereitstellung des EDS-Files
- Operating temperature : -40°C … +80°C
- Storage temperature : -40°C … +120 °C
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!