T-200.L 24V configure
NP-25X configure
QFS-2X configure
MO configure
TK-300 configure
TK-101 configure
T-200.L 24V
Leakage probes with general building authority approval
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Head : Polyethylenanschlusskopf (PE)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24...30 V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
NP-25X
Pneumatic level switch
Reliable & simple probe for sensing aggressive, sticky or heavily contaminated liquids, especially suitable as overflow protection.
Properties NP-250 | NP-252
- Connection head : PA
- Protection class EN60529 Connection head : IP 54
- connection thread : ab G½”
- Container connection flange : ab DN 25
- Pitot tube material : PVC
- Material Screw connection : PVC
- Material flange : PVC
- Hose Ø : 16 mm / 25 mm
- Operating temperature : max. +60 °C
- medium temperatur : max. +60 °C
- Contact : Wechsler
- Switching voltage silver : 250 V AC
- Switching voltage gold : 24 V AC
- Switching current silver : 6 A
- Switching current gold : 100 mA
Properties NP-251 | NP-253
- Connection head : PS
- Protection class EN60529 Connection head : IP 54
- connection thread : ab G½”
- Container connection flange : ab DN 25
- Pitot tube material : 1.4571
- Material Screw connection : 1.4571
- Material flange : 1.4571
- Hose Ø : 15 mm / 28 mm
- Operating temperature : max. +60 °C
- medium temperatur : max. +90 °C
- Contact : Wechsler
- Switching voltage silver : 250 VAC
- Switching voltage gold : 24 V AC
- Switching current silver : 6 A
- Switching current gold : 100 mA
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
- Pressure range : 0...2.000 bar gestuft
- supply : 24 V DC
- Output : Relais 60 V AC/1A
- overload : 1,5 x Messbereich
- Med. connection : G 1/4 Zoll
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
- Protection class EN60529 : IP68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Operating pressure (QFS-20) : max. 15 bar
- Operating pressure (QFS-21) : max. 6 bar
MO
Monostable Switch
Properties
- Protection class : IP 65
- Switching current : max. 1 A
- Switching voltage : max. 24 V
- Switching capacity : max. 20 W/VA
Material
- Housing : Messingrohr Ø 10 x 1
- Cable : TPK (PVC basis) | SIL (Silikon)
Operating temperature
- TKP : –15 ° ... + 60 °C
- SIL : –15 ° ... +130 °C
T204-0.F
Immersible Magnetic Probe for Ex Zone 0 (Cat. 1)
The T20... magnetic immersion probes are used to detect fill level limits in containers for liquid media, where an explosive atmosphere of Zone 0 (Cat. 1) exists in the gas space above the liquid and an Ex-Zone 1 (Cat. 2) exists outside the container in the area of the junction box.
Properties
- connection : Kabel PUR blau
- Protection class : IP 68 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- min. contact gap type 04 : 85 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 10 (14)
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
- CE marking : siehe Konformitätserklärung
Operating temperature
- PV : max. 60°C
- PE : max 80 °C
- PP : max. 90°C
MaterialDensity
- Type 10 : 0,72 g/cm³
- Type 14 : 0,72 g/cm³
- Type 18 : 0,82 g/cm³
TK-101
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff
- LCD display : optional
- Signal output : 0…10 V | 4…20 mA
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
Operating conditions
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!