Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
PO/ET-520
ltdata.Polyethylenanschlusskopf
:
PE/ET-521
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24…300V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
–25...+70 °C
Wire cross-section max.
:
1,5mm²
Switching point distance between two contacts
:
min. 40 mm
Switching hysteresis
:
ca. 10-15 mm
Material
Housing
:
Polycarbonat
Mounting clip
:
V2A, Kabelbinder (PP)
Rivet
:
V2A
Screw connection
:
M 20 x 1.5, Polyamid
Weight
BK-390-50
:
137 g
BK-390-63 / BK-380
:
140 g
Switching contact
Switching voltage
:
5...250 V AC/DC
Switching current
:
1mA...6 A AC/DC
Switching capacity(min.)
:
300 VA, 60 W
Switching capacity(max.)
:
5 mW
QFS-1X
Float switch with reed switch (mercury-free)
Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Properties
Protection class EN60529
:
IP 68
Cable entry
:
PVC , PTFE
Conductor cross-section
:
3 x 0,75 mm², PUR 3x0,5mm²
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC (QFS-11 nur NO oder NC)
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Float
Material Float
:
PE (Polyethylen)
ltdata.
:
ltdata.
:
ltdata.
:
Operating temperature
TPK(V), AEM
:
max. + 60 °C
PUR
:
max. + 70 °C
Silicone,Tefloncable with PE float
:
max. + 80 °C
Operating pressure
Cylinder
:
max. 1 bar
Sphere
:
max. 2 bar
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
connection
:
G 1” (andere Gewinde auf Anfrage)
max.length guide tube
:
siehe Diagramm
Operating temperature
:
atmosphär. Bedingungen
Operating pressure
:
atmosphär. Bedingungen
media density
:
siehe Eintauchtiefe
Number of contacts
:
beliebig
Contact load
:
max. 10 VA, max. 230 V AC
Length
:
max. 1750 mm
Material
Sight tube
:
PVC transparent
connection
:
PVC-Verschraubung mit PTFE-Stangenführung
Guide rod
:
Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
float
:
PE / PP
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff mit LCD-Anzeige (oponal)
Overpressure
:
1,2* (1,5*) x Nenndruck
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Signal output selection
:
0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
Pressure range
:
5…1.000 bar
Operating conditions
Operating voltage
:
14...28 VDC ± 10 %
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
Connections
Electrical connection
:
Schraubklemme im Gehäuse
Process connection
:
G1/4" (andere auf Anfrage)
Our application engineers advise you