Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
Power supply
:
230 V AC
measuring range (CO2)
:
0..10.000 ppm
Measuring accuracy CO2
:
± 50ppm +3 % vom Messwert
Operating conditions
:
0…50°C / 0…85 %rH
Storage conditions
:
-30…70°C / 0…85 %rH
Protection class
:
IP 31
EMV/ESD
:
EN 50082-1, EN 50082-2
Signal output
:
I²C
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
MKL
Magnetic Flap Indicator
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
connection
:
Flansch ab DN 15
Material
:
rostfreier Edelstahl, PVC, PPH, PVDF
Material flange
:
Edelstahl 1.4571, C22.8
Material Float
:
Edelstahl, Titan, PVC, PPH, PVDF
Number of contacts
:
beliebig
Contact load
:
max 10 VA, max 230 V AC
Display length
:
max. 6m
Operating temperature
PTFE seal
:
max. 150 °C
Stainless steel: Klingerit seal
:
max. 200 °C
PVC
:
max. 60 °C
PPH
:
max. 90 °C
PVDF
:
max. 130 °C
Stainless steel float
Weight
:
~ 300 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
16 bar
media density
:
ρ ≥ 0,70 g/cm³
Stainless steel float
Weight
:
~ 320 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
40 bar
media density
:
ρ ≥ 0,75 g/cm³
Titanium float
Weight
:
~ 180 g
Dimensions
:
Ø 52 x 150
Operating pressure
:
16 / 40 bar
media density
:
ρ ≥ 0,73 g/cm³
PVC float
Weight
:
~ 331 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,8 g/cm³
PPH float
Weight
:
~ 283 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,69 g/cm³
PVDF float
Weight
:
~ 352 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,85 g/cm³
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
Pressure range
:
0...500mbar gestuft
supply
:
12 - 24 V DC
Output
:
Relais 230 V/1A
overload
:
2 x Messbereich
Med. connection
:
Schlauch
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
Our application engineers advise you