The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
Tank connection
:
Flansch ab DN 25 oder Verschraubung ab G ½"
Material Float
:
PPH max. 2,5 bar, Glas max. 10 bar
cable length
:
bei monostabilem Kontakt: Standard 2 m
Number of contacts
:
beliebig
Contact distance
:
min. 10 mm
Temperature of the fluid
:
mit Plexiglasrohr max. +70 °C
media density
:
ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
Material tube sight glass
:
transparentes PVC
Temperature of the fluid
:
max. +60 °C
Operating pressure
:
max. 2,5 bar
Material flange
:
PVC
Material connection with angle valve
:
PVC
Material sealing ring
:
Gummi
Properties W-351
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Rotguss
Material connection with angle valve
:
Rotguss
Material sealing ring
:
Silikon
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
Properties W-352
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Edelstahl
Material connection with angle valve
:
Edelstahl 1.4571 als Bogen 90°
Material sealing ring
:
PTFE und Viton
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
Properties W-353
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Edelstahl
Material connection with angle valve
:
Edelstahl 1.4401
Material sealing ring
:
PTFE und Viton
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class Socket
:
IP65
Float type
:
Typ 07
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10mm |15 mm | 20 mm
Accessories
:
R/I-Wandler TK-101
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
2 Wechselkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ltdata.
:
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
TK-30X
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
connection thread
:
G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
connection cable
:
LiYY max. 80 °C | Silikon max. 130 °C
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
Operating pressure
:
max. 20 bar je nach Ausführung
media density
:
siehe Schwimmerdaten
Viscosity
:
< 100 cp
Switching hysteresis
:
ca. halbe Auflösung
Resolution
:
7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
Total resistance
:
ca. 5 kΩ
Measuring voltage
:
max. 24 V
Measuring current
:
max. 5 mA
Our application engineers advise you