Level Sensors for Pump Control

Fluid.iO supplies level sensors, evaluation units and switching relays for level-based pump control in sumps, shafts and tanks. Compare point level switches and continuous level sensors, then see how each can be used to start and stop pumps or trigger alarms in filling and emptying applications.

Pump Control with Fluid.iO | Sensing Fluid Excellence

Why reliable level sensing matters: A pump is only as reliable as the signal that switches it

For more than 25 years, Fluid.iO has been developing, manufacturing, and selling durable and reliable level measurement instruments and systems for a wide range of applications and liquids across all industrial sectors, including water and wastewater, chemicals, and mechanical engineering with their brand E.L.B. Füllstandsgeräte.

Jump to:

Challenges & Risks in Pump Control

Dry Running

A pump that runs without liquid overheats and destroys seals and bearings within minutes.

Overflow

A pump that starts too late floods sumps, shafts and basins –or spills hazardous media.

Wear and Tear

Switching points set too close together wear out motors and contactors and waste energy.

Compliance

Water-hazardous liquids and explosive atmospheres call for approved devices.

Fluid.iO has you covered! With our portfolio we can answer all four. Our solutions sense the level, evaluate it, switch the pump safely.

System Architecture: One Control Loop

3 Technology Areas for Maximum Safety for the Environment

SENSE

Level & Limit

  • Float switches QFS / QFSK
  • Magnetic probes T200
  • Hydrostatic probes HD-1XX
  • Ultrasonic LU-150 / LU-180
  • Electrodes HE / EF

EVALUATE

Set points & Display

  • Relays XR
  • Integrated electronics ET
  • Evaluation units TK-313 / TK-315
  • LED bar display TK-32X
  • Digital display AD-310

ACT

Pump & Alarm

  • Contactor or motor starter
  • Contact protection XR-6x0
  • PLC / SCADA via 4–20 mA
  • Alarm unit OAA-300
  • Standby pump on peak load
Independent Safety Layer: Overfill Protection and leak probes with line-monitored relays –separate from the operational control.

The two measurement technologies to switch a pump

Point Level Measurement

A switch changes state at a fixed height. Two switching points –or one two-point switch –give the ON/OFF hysteresis.


  • Simple, robust, low cost
  • Often no sensor supply needed
  • Switching points fixed by installation

Best for: drainage sumps, small tanks, single pumps

All level sensors in this category

Continuous Level Measurement

A sensor delivers 4–20 mA over the full range. Set points are adjusted on the evaluation unit –no reinstalling.


  • Several set points from one sensor
  • Level display in %, m or litres
  • Signal available for PLC / SCADA

Best for: wells, process tanks, multi-pump stations

All level sensors in this category

Fluid.iO offers Level sensors for (almost) every liquid and application.

The following table shows common level measurement solutions for pump control.

Product
Principle
Output
Typical use
QFS-12
QFS-12
show product
Two-point float switch (PE) Changeover contact ON/OFF control of one pump
QFS-10
QFS-1X
show product
Reed float switch, mercury-free Changeover, NO or NC Simple level switching
QFSK-2X
QFSK-2X
show product
Stainless float switch combination MIN + MAX contacts Separate ON and OFF levels
NSP-X-E
NSP-X-E
show product
Vibrating limit switch Switching output Dry-run protection, tanks & pipes
Electrodes
EE-24
show product
Conductive Electrode Via XR / ER Relay On-site display, BK contacts
BK-390
BK-390
show product
Mechanical: float, rope, counterweight On-site display, BK contacts Large tanks, no power needed
HD-1XX
HD-1XX
show product
Hydrostatic probe, 0.8–10 mWS 4–20 mA, 2-wire Wells, shafts, boreholes
LU-150 / 180
LU-1X0
show product
Ultrasonic, non-contact, ≤ 5 m 4–20 mA, 2-wire Dirty media, sludge; Ex (LU-180)
TK-30X
TK-30X
show product
Magnetic probe, quasi-continuous Stepped level signal Foaming or changing media

Also available: PTFE float switches QFS-5x / 6x for hot or aggressive liquids up to 150 °C, and Ex-approved variants across the range.

Evaluate & Switch

From signal to switching command – we offer four device families for evaluation and switching of level signals, from simple relays to evaluation units with display and set points.

EVALUATION UNITS

TK-31x

TK-313
  • TK-313: 2 changeover limit contacts
  • TK-315: 4 NO limit contacts
  • 4–20 mA input (TK-315 also 0–10 V)
  • Level in %, DIN rail
TK-31X Details

DISPLAYS

AD-31x · TK-32x

AD-310
  • AD-31x: programmable digital display
  • Scaling to m, litres or %, alarm relays
  • TK-32x: LED bar display
  • Bright LEDs for harsh environments
AD-31X Details

RELAYS

XR-6xx · XR-4xx

XR Relais ATEX
  • XR-6xx: contact protection for float and reed contacts
  • XR-4xx: electrode relays for conductive probes
  • Dry-contact outputs up to 5 A
  • ATEX and IECexvariants
XR-6X2 Details

ALARM

OAA-300

OAA-300
  • Optical-acoustic alarm unit
  • 1 to 4 channels
  • IP65 housing
  • Designed for overfill and leak alarms
OAA-300 Details

Pump Control Examples & Sensor Applications

Explore real-world use cases and applications of our pump control solutions.

Animation of Large tank –mechanical indicator MTA + BK
Pump sump with dry-run protection

One hydrostatic probe and one TK-315 –four set points from a single 4–20 mA signal.

Relay Function
K1 High-high: alarm via OAA-300, start standby pump
K2 High: pump ON
K3 Low: pump OFF
K4 Low-low: pump locked out, alarm

wiring diagram Pump sump with dry-run protection

Animation of Large tank –mechanical indicator MTA + BK
Chemical tank with T200 probe
Three floats on one guide tube, each held between stop rings –every contact reports a steady state.
Contact Function XR Input
Float 1 · K1 High alarm XR-620 CH2 · E6
Float 2 · K2 Pump ON (max) XR-620 CH1 · E1
Float 2 · K3 Pump OFF (min) XR-620 CH1 · E2
Float 3 · K4 Dry-run lockout XR-610 · E1

wiring diagram Pump sump with dry-run protection

Animation of Large tank –mechanical indicator MTA + BK
Drainage pit with QFS-30 floats
Two mercury-free float switches and one two-channel XR-620 –pump control and high alarm.
Float Function XR Input / Output
A: QFS-30, hysteresis Pump ON and OFF CH1 · E1 →11/14
B: QFS-30, NO High alarm CH2 · E6 →21/24

Drainage pit with QFS-30 floats

Simplified –in Ex zone 1 use the ATEX version XR-6x2. Contact types and DIP settings per XR manual.
Animation of Large tank –mechanical indicator MTA + BK
 Pump shaft –electrodes + XR relay (Emptying)
The rod lengths set the levels; a two-channel XR-420 does pump control and alarm.
Rod Function XR-420 Input / Output
K1 High alarm CH2 · E6 →21/24
K2 (max) Pump ON CH1 · E1 →11/14
K3 (min) Pump OFF CH1 · E2
Ref (longest) Reference E0 and E5

Drainage pit with QFS-30 floats

Animation of Large tank –mechanical indicator MTA + BK
left content
right content
Animation of Large tank –mechanical indicator MTA + BK
left content
right content

Selection Guide Level Sensors and Evaluation Units for Pump Control

Which combination fits your application?

Drainage sump with a single pump

Drainage sump with a single pump

In a drainage sump, the pump needs to start when the water reaches the upper switching level and stop once the water drops to the lower switching level. QFS-12 or QFS-30 float switches detect the required switching levels. The XR-6x0 processes the signals and operates the contactor that switches the pump, automating drainage based on the water level.

  • Recommended products: QFS-12 or QFS-30
  • Recommended Evaluation Unit: XR-6x0 → contactor
Well or borehole with display

Well or borehole with display

In a well or borehole, the water surface is often far below the point of access. An HD-100 or HD-102 hydrostatic probe continuously measures the water level using the pressure of the water column. The AD-310 displays the measured level at an accessible location, allowing operators to see how it changes during pumping.

  • Recommended products: HD-100 or HD-102
  • Recommended Evaluation Unit: AD-310
Multi-stage sump or tank

Multi-stage sump or tank

A sump or tank with multi-stage control requires different actions at different levels. For example, one level may start a pump, while a higher level triggers an alarm. An HD-1XX series sensor or an LU-150 provides a continuous level signal. The TK-315 and OAA-300 process that signal to trigger the corresponding action at each configured threshold.

  • Recommended products: HD-1XX series or LU-150
  • Recommended Evaluation Unit: TK-315 and OAA-300
Conductive liquids in shafts

Aggressive media with multiple switching levels

When a tank contains an aggressive liquid, the wetted materials must be compatible with the medium. The application may also require several switching levels for functions such as fill control and a high-level alarm. A T200 in PPH or PTFE can detect multiple switching levels, with the material selected for the liquid in use. The XR-6x0 relay processes the signals and passes them to the control system.

  • Recommended products: T200, PPH / PTFE
  • Recommended Evaluation Unit: XR-6x0 relay
Conductive liquids in shafts

Conductive liquids in shafts

An HE multi-electrode probe can detect several switching levels in a shaft containing a conductive liquid. When the liquid reaches an electrode, it creates a conductive path to the reference electrode. The XR-4x0 relay detects this change. Electrodes positioned at different heights can provide separate pump start and stop signals, for example.

  • Recommended products: HE Multi-Electrode
  • Recommended Evaluation Unit: XR-4x0 relay
Compact level monitoring with integrated electronics

Compact level monitoring with integrated electronics

In compact installations, space for additional components in the control cabinet can be limited. The 24 V versions of the EF 3 through EF 5 can be used with an integrated ET board for level monitoring. The board processes the sensor signal within the unit, eliminating the need for a separate evaluation relay in the control cabinet.

  • Recommended products: EF 3…5 24 V
  • Recommended Evaluation Unit: Integrated electronics board
Large tank with a local level display

Large tank with a local level display

Operators working at a large tank need to read the level locally, while the control system may need to respond automatically at defined thresholds. The MTA level indicator displays the level at the tank. BK contacts signal the specified switching levels to the XR-6x0, which can operate a contactor to switch a transfer pump, for example.

  • Recommended products: MTA + BK contacts
  • Recommended Evaluation Unit: XR-6x0 → contactor
Point level detection in explosive atmospheres

Point level detection in explosive atmospheres

In potentially explosive atmospheres, the sensor, evaluation unit, and installation must meet the requirements of the measurement location. Depending on the application, a T200 Ex or an Ex-QFS-3x float switch can be paired with the ATEX-rated XR-6x2. The XR-6x2 processes the point level signal for the control system. The specific combination depends on the hazardous area classification, the medium, and the approvals for each device.

  • Recommended products: T200 Ex · Ex-QFS-3x
  • Recommended Evaluation Unit: XR-6x2 (ATEX)

Safety & Compliance

Approvals built in, not bolted on

Water Resources Act

Approved overfill protection and leak probes for water-hazardous liquids

ATEX / IECEx

Float switches, electrodes, probes and ultrasonic sensors for Ex zones 0 and 1

SIL 2

Optional SIL 2 versions of electrodes and XR relays

ISO 9001

Certified by TÜV Nord, VDMA member, developed and made in Germany

Use these devices as the independent safety layer next to the operational pump control.

Get Help Selecting a Level Sensor or request a quote

Our team looks forward to your inquiry

Your ways to contact us:

info@fluidio.de +49-6251-8462-0

Choose Fluid.iO as your technology partner for measuring and monitoring fill levels and for controlling pumps.

  • We are specialists in measurement, monitoring, and control technology for liquids and gases.
  • We possess decades of experience and a strong reputation in level measurement technology through our brand, E.L.B. Füllstandsgeräte.
  • We offer sensors and evaluation units, available either as standalone devices or as complete measuring systems.
  • Benefit from our extensive range of measurement principles and materials, suitable for almost any level measurement application and industry.
  • With our partner and distribution network, we can ensure expert advice and on-site service almost anywhere in the world.

German Producer - Global Supplier


"Made in Germany" - We produce in Germany and deliver worldwide
We have distributors in many industrialized nations worldwide

Find a distributor

Our know-how in process measurement technology is your competitive advantage

  • Standard sensors and devices for process measurement, air conditioning and refrigeration technology
  • customization and development
  • Application and sensor consulting for all types of fluids
  • Problem analysis and development of proposed solutions
As a technology partner, we are at your side with our worldwide sales network

Application consulting

Together with our application engineers, you will find the right device to sustainably increase the safety and efficiency of your processes.

Commissioning support

After consultation and ordering, we will support you until the measuring device is working optimally at its intended location.

Logo of Fluid.iO Sensor + Control

Fluid.iO
Sensor + Control
GmbH & Co. KG

Gernsheimer Straße 19
D-64673 Zwingenberg
Tel.: +49-6251-8462-0
E-Mail: info@fluidio.de