KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose :
- ltdata.Aluminiumdose :
- ltdata.Polyethylenanschlusskopf :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- ltdata.BetriebstemperaturPP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
KST-20 Calima
Climate control for automatic & controlled dehumidification, ventilation and cooling of rooms
The KST-20 Calima climate control system with aH-Controlled technology for ventilation and dehumidification for all types of private, commercial and industrial rooms. With the operating modes for living room ventilation and room dehumidification, the KST-20 Calima can be used flexibly in almost all living, working and industrial areas.
Specifications
- measuring range (Humidity) : 0…100% rF,
- Measuring accuracy (humidity) : ±2%
- measuring range (Temperature) : -40…+80°C
- Measuring accuracy (temperature) : ±0,2°C
- Signal output : I2C
- Connections for actuators : Zwei Steuer- und Schaltausgänge für Zuluft- und Abluftelemente
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 140x140x46 mm
Connection options
- Dehumidification : Einstufige Lüftungsventilatoren
- Room dehumidification / living space ventilation : Zweistufige Lüftungsventilatoren
- Living space ventilation / Dehumidification : Drehzahlgesteuerte Ventilatoren 0…10 V DC
Operating conditions
- Temperature : 0...50 °C
- RelativeHumidity : 85 % nicht kondensierend
- EMV/ESD : EN50082-1/2
MKL
Magnetic Flap Indicator
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
- connection : Flansch ab DN 15
- Material : rostfreier Edelstahl, PVC, PPH, PVDF
- Material flange : Edelstahl 1.4571, C22.8
- Material Float : Edelstahl, Titan, PVC, PPH, PVDF
- Number of contacts : beliebig
- Contact load : max 10 VA, max 230 V AC
- Display length : max. 6m
Operating temperature
- PTFE seal : max. 150 °C
- Stainless steel: Klingerit seal : max. 200 °C
- PVC : max. 60 °C
- PPH : max. 90 °C
- PVDF : max. 130 °C
Stainless steel float
- Weight : ~ 300 g
- Dimensions : Ø 52 x 270
- Operating pressure : 16 bar
- media density : ρ ≥ 0,70 g/cm³
Stainless steel float
- Weight : ~ 320 g
- Dimensions : Ø 52 x 270
- Operating pressure : 40 bar
- media density : ρ ≥ 0,75 g/cm³
Titanium float
- Weight : ~ 180 g
- Dimensions : Ø 52 x 150
- Operating pressure : 16 / 40 bar
- media density : ρ ≥ 0,73 g/cm³
PVC float
- Weight : ~ 331 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,8 g/cm³
PPH float
- Weight : ~ 283 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,69 g/cm³
PVDF float
- Weight : ~ 352 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,85 g/cm³
ELH 24 V
Hanging electrode as leakage probe 24 V DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
TK-307
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Connection housing : Aluminium H 30 mm x B 50 mm x T 45 mm
- Connection socket : Polyester H 55 mm x B 80 mm x T 45 mm
- Protection class socket / plug : IP 65
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution depending on type : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101