Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
CS-11
CO2 Sensor with digital Interface
Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
Measured variable:
:
CO2
Measuring range:
:
0…5.000 ppm
Measuring principle:
:
optisch, NDIR
Housing
:
Kunststoff
measuring grid
:
2 sec.
Accuracy
:
± 50 ppm
Protocol
:
I²C-Bus
Operating conditions Temperature
:
-0°C … 50°C
Operating conditions Humidity
:
0…85 % rH
Storage conditions Temperature
:
-30°C … 70 °C
Storage conditions Humidity
:
0…85 % rH
Properties MV-CAN
Housing
:
Plastik
Mounting
:
Hutschienenmodul für Einbau in Schaltschrank
Operating voltage
:
10…48 V
measuring grid
:
2 sec.
CAN protocol
:
CANopen 2.0 A nach CiA DS 404
Physical Layer
:
nach ISO 11898
Option
:
Bereitstellung des EDS-Files
Operating temperature
:
-40°C … +80°C
Storage temperature
:
-40°C … +120 °C
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
Protection class
:
IP 68
Probe body material
:
PE, PVC, PPH, PVDF
Diameter probe body
:
15 mm, 25 mm, 40 mm
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
: