Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
Ex-QFS-3x
Mercury-free float switches with Ex approval
These float switches have a mercury-free switching system consisting of a microswitch and a ball which actuates this switch.
Technical Data
- Protection class EN60529 : IP 68
- Material Float : PP
- Cable : TPK (PVC Basis), PVC Basis verstärkt, Polyurethan, Silikon, Teflon, Ethylen-Acrylat-Kautschuk
- Conductor cross-section : 3x 0,75 mm², Polyurethan 3x 0,5 mm²
- Operating temperature TPK(V) : AEM Kabel max.+ 60 °C
- Operating temperature PUR cable : max.+ 70 °C
- Operating temperature SIL, FEP cable : max.+ 85 °C
- Operating pressure : max. 1 bar Zylinder| max. 2 bar Kugel
- Switching system : Mikroschalter
- Contact type : Wechsler, NO, NC
- Electrical connection data, Ex-protection : siehe EG-Prüfbescheinigung TüV 09 ATEX 555342
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- CE marking : siehe Konformitätserklärung
- Weight : ca. 200 g
Media density Ex-QFS-30
- TPK(V) cable : ρρ 0,85 g/cm³
- PUR cable : ρρ 0,95 g/cm³
- SIL cable : ρρ 0,90 g/cm³
- FEP cable : ρρ 0,95 g/cm³
- AEM Cable : ρρ 0,90 g/cm³
Media density Ex-QFS-31
- Sphere : ρρ 0,60 g/cm
Mounting position
- Ex-QFS-30 : waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
- Ex-QFS-31 : waagerecht mit Flansch ab DN 100 (PP)
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
- Switch housing : PPH| PVDF
- Seal : NBR (PPH) | FPM (PVDF)
- Operating temperature : PPH max. 80 °C| PVDF max. 100 °C
- Operating pressure : max. 10 bar
- Mounting position : horizontal (±30° von der Horizontalen)
- Contact assembly : Schliesser-, Öffnerkontakt (je nach Einbau)
- Electrical connection : PVC-Kabel
- Switching capacity : max. 230 V AC/DC| max. 40 VA, max. 2 A
- Contact resistance : max. 80 mW
- Min. electric strength : 400 V DC / 1 s
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- fluid density : PPH > 0,6 kg/dm³ | PVDF > 0,95 kg/dm³
- Protection class : IP 68
Connections
- external installation : G ½"
- internal installation : M16
Fluidix Lub-VDT
Oil condition sensor for permanent monitoring of mechanical properties of liquids
The FluidIX Lub-VDT enables inline monitoring of mechanical fluid properties.
Properties
- CE marking : EN 61000-6-1/2/3/4
- Operating voltage : 9...32 V DC
- Housing material : Edelstahl
- Protection class : IP 67
- Dimensions : 30x90 mm
- Process connection : G 3/8"
- Electrical connection : M12-8 A-Coding
- Weight : 150g
- Measurement output : 2x 4...20mA
- bus protocol : ModbusRTU, CANopen
Measured variables
- Resonator frequency : 20...25 kHz
- Viscosity : 1-650 cSt (mm²/s)
- density : 0.5-1.5 g/cm³
- Temperature : -40...+125°C
- sampling rate : 1/s
Operating conditions
- Temperature of the fluid : -40...+125°C
- Housing temperature : -40...+100°C
- oil pressure : Max. 50 bar
- particle size : 250 μm
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
EF2 24...230 V
Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G1"
- Union nut : auf Wunsch
Material
- Screw connection : PE, PVC, PPH, PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Sensitivity range : einstellbar 2…100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PTFE : 100 °C
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : < 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC /30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED Grün, Funktions-LED Rot
- Switching delay : ca. 0,5 s Anzug / Abfall
- CE marking : siehe Konformitätserklärung
T200
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ZMF-202e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0...17.000ppm : 0…1,7 vol% (100 % LEL)
- 0...21.000ppm : 0…2,1 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :