Cart
product added to request
T-200.L configure
EFV2 20…230V configure
XR-4x2 configure
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Box : Polyethylen-Anschlusskopf (PE)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
EFV2 20…230V
Conductive electrodes with 24...230 V direct connection
The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾" | S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Kohlestifte
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Adjustable sensitivity range : 2..100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Power supply
- nominal voltage : 24...230 V AC/DC
- Power consumption : ≤ 2 W
Output
- potential-free changeover contacts : 2
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs- LED grün Funktions-LED rot
- Switching delay : ca. 0,5 s
T202
Immersible Magnetic Probe made of stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
XR-4x2
Electrode relay with ATEX and WHG approval
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
- Housing : Aluminium
- Protection class : IP30
- Dimensions : 197 x 153 x 37,5mm (B x H x T)
- Temperature range : 0 – 50°C
- Supply voltage : 24V DC +/-20%
- Power consumption : 120mA – 220mA
- Reverse polarity protection : ✓
- Display : 4x20
Outputs
- analog 0(4)–20mA : 3x
- digital : 4x
- fixed for alarm : 1x
- free configurable : 3x
display of measured value
- Flow velocity :
- Filling level :
- flow :
- flow rate :
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!