XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
- Quiescent current : umschaltbar
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
- Measuring range : -40…+80 °C
- deviation : ± 0,3 K (10...80 °C)
- Measuring element : Halbleiter-Diodenfühler
- measuring resolution : 0,1 K
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 10...48 V
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
- Minimumairspeedrequiredformeasurementacrossthesensor : 1,5 m/s
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
TSR-CAN-03
CANopen transmitter for temperature measurement in media
High-quality stainless steel transmitter for precise temperature measurement in all stainless steel-compatible media
Measurement parameters
- Measuring range : -40…+80 °C (optional +150°C)
- deviation : ± 0,3 K (-40…+80 °C)
- Measuring element : Halbleiter
- measuring resolution : 10 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 12…27 V ±20 %
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Box : Polyethylen-Anschlusskopf (PE)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
T205 VA
Stainless steel magnetic immersion probes
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : max. 2x Typ 08
- connection cable : Silikon Litze
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar (Zylinder)
- Number of contacts : max. 2 x Schließer/ Öffner wahlweise durch 180°-Drehung des Schwimmers bei 2 Schwimmern
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
- Sliding tube length : max. 1000 mm
- media density : Typ 08: 0,78 g/cm³
- float : Zylinder Edelstahl 1.4571 27 mm Ø
- min. contact distance with several floats : 50 mm
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
- Dimensions : 180 x 48 x 36,5 mm ( L x B x H )
- Weight : ca. 1,5 kg
- Protection class : IP68
- Cable length (standard) : 15 m
- Bending radius : > 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
- Temperature range : 0°C ... 50°C
- Mounting shoe material : V2A 1,5mm
Certificates
- EX / ATEX : IBExU 04 ATEX 1256
Measuring principle
- Flow velocity: Ultrasonic Doppler :
- Filling level: Differential pressure :
Flow velocity
- Measuring range : 0,01 - 4 m / s
- Measuring accuracy : +/- 5 % vom Momentanwert im Kanal
- Temperature drift : 0,1% / °C ( Meßspanne )
- Temperature drift : 0,05% / °C ( Nullpunkt )
- Output signal : 4 - 20 mA
Filling level
- Measuring ranges : 0 –1 m ; 0 – 2 m ; 0 – 4 m
- Measuring accuracy : < 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
- Temperature drift : 0,005% / °C v.E. Meßspanne
- Temperature drift : 0,005% / °C v.E. Nullpunkt
- Material : Al2O3 (96%) aktive Fläche
- Output signal : 4 – 20 mA
- Zero point : norm 4 mA ( +/- 3 % )
Our application engineers advise you personally, comprehensively and professionally!