Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties TPS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…100% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-50...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class Socket
:
IP65
Float type
:
Typ 07
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10mm |15 mm | 20 mm
Accessories
:
R/I-Wandler TK-101
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
ltdata.Aluminiumdose
:
ltdata.Polyethylenanschlusskopf
:
Cable
:
Plug
:
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Operating temperature
:
atmosphärisch
ltdata.BetriebstemperaturPP
:
max. 90°C
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
Our application engineers advise you