Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
TK-320
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-321
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-322
:
19” Karteneinschub 7 TE, 3 HE
Properties
Protection class EN60529
:
IP 52
Operating temperature
:
– 20 °C...+60 °C
nominal voltage
:
24 V DC...230 V AC
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | Bürde max. 500 Ω
Relay
:
2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
Number of LEDs
:
33 (rot/grün); 32 (TK-322)
Resolution
:
ca. 3,5 %
Error
:
± 1 LED
connection
:
Schraubklemmen
connection TK-322
:
Steckerleiste
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | max. load 500 Ω
Relay(2xSwitch)
:
max. 230 V | min. 5 V
Relay(2xSwitch)
:
max. 3 A | min. 1 mA
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
ltdata.Aluminiumdose
:
ltdata.Polyethylenanschlusskopf
:
Cable
:
Plug
:
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Operating temperature
:
atmosphärisch
ltdata.BetriebstemperaturPP
:
max. 90°C
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
Our application engineers advise you
personally, comprehensively and professionally!