Electrical connection
:
DIN EN 175301-803 A | DIN EN 175301-803 C | Binder M12x1 (Serie 713)
Process connection
:
G 1/4" ISO 1179-2 (Male Form E) | 1/4" NPT | 7/16" 20 UNF Male
measuring range (bar)
:
0…0,6 | 0…600
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40°C...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Our application engineers advise you
personally, comprehensively and professionally!