Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
Power supply
:
230 V AC
measuring range (CO2)
:
0..10.000 ppm
Measuring accuracy CO2
:
± 50ppm +3 % vom Messwert
Operating conditions
:
0…50°C / 0…85 %rH
Storage conditions
:
-30…70°C / 0…85 %rH
Protection class
:
IP 31
EMV/ESD
:
EN 50082-1, EN 50082-2
Signal output
:
I²C
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
Protection class EN60529
:
IP68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Operating pressure (QFS-20)
:
max. 15 bar
Operating pressure (QFS-21)
:
max. 6 bar
HD-1XX