Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G1"
- Union nut : auf Wunsch
Material
- Screw connection : PE, PVC, PPH, PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Sensitivity range : einstellbar 2…100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PTFE : 100 °C
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : < 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC /30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED Grün, Funktions-LED Rot
- Switching delay : ca. 0,5 s Anzug / Abfall
- CE marking : siehe Konformitätserklärung
KST-20 Calima
Climate control for automatic & controlled dehumidification, ventilation and cooling of rooms
The KST-20 Calima climate control system with aH-Controlled technology for ventilation and dehumidification for all types of private, commercial and industrial rooms. With the operating modes for living room ventilation and room dehumidification, the KST-20 Calima can be used flexibly in almost all living, working and industrial areas.
Specifications
- measuring range (Humidity) : 0…100% rF,
- Measuring accuracy (humidity) : ±2%
- measuring range (Temperature) : -40…+80°C
- Measuring accuracy (temperature) : ±0,2°C
- Signal output : I2C
- Connections for actuators : Zwei Steuer- und Schaltausgänge für Zuluft- und Abluftelemente
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 140x140x46 mm
Connection options
- Dehumidification : Einstufige Lüftungsventilatoren
- Room dehumidification / living space ventilation : Zweistufige Lüftungsventilatoren
- Living space ventilation / Dehumidification : Drehzahlgesteuerte Ventilatoren 0…10 V DC
Operating conditions
- Temperature : 0...50 °C
- RelativeHumidity : 85 % nicht kondensierend
- EMV/ESD : EN50082-1/2
ZS-1
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...0,25mbar :
- 0...0,5mbar :
- 0...1mbar :
- 0...2,5mbar :
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
- Housing : Kunststoffgehäuse*
- Dimensions (LxBxH) : 18 x 90 x 62 mm
- Internal circuits : Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
- Fieldbus and I/O level : getrennt durch galvanische Trennung
- ltdata.*zumAufrastenaufDIN-Trageschienen :
ElectricalConnection
- Operating voltage : 11...32V DC (typ. 24V DC)
- Operating temperature : 0...+55 °C
- Operating temperature : optional -40...+70 °C
- Conductor cross-section : 0,08...1,5 mm² (AWG28...AWG14)
CAN bus properties
- baud rate (max.) : 1 MBit
- ciA Standards : Ds301 Version 4.2 & DS401 Version 3.0
- ISO standards : ISO11898 (+ Transceiver TJA1050)
- PDO : siehe Dokumente
LU-180 EX
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
LU-150
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : 1x Typ 12 | 1x Typ 13
- connection cable : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : max. 60 °C
- Operating pressure : drucklos
- Number of contacts : 1x Schließer / Öffner
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
Float type
- Type 12 : Zylinder PP 19 mm Ø | Dichte 0,93 g/cm³
- Type 13 : Zylinder PP 25 mm Ø | 0,68 g/cm³
TRM-100
Turbidimeter (0...1.000 FNU or 500...4.000 FAU)
The turbidimeter TRM-100 is a compact device for measuring turbidity in liquids. The "turbidity" is measured using the scattered light method (angle 90 degrees) for the turbidity range of < 1,000 FNU (Formazine Nephelometric Units) and the transmitted light method (angle 0 degrees) for the turbidity ranges > 1,000 FAU (Formazine Attenuation Units).
Properties
- Operating pressure : max. 10 bar @ 20 °C | max. 2,5 bar @ 60 °C
- Measuring range : 500...4.000 FNU / FAU
- Measuring accuracy : +/-5 %
- Mounting position : horizontal
- Process connection : DN 20 | DN 40
- Flange connection : >= DN 20
- number of senders : 2
- number of receivers : 1
Material
- Seal : EPDM | optional FPM (Viton)
- Process connection : PVC | PPH
- Measuring tube : Borsilikatglas mit Nano Beschichtung
Input
- Power supply : 18...30 V DC
- Power consumption : < 2 W
Output
- Output contact : 4...20 mA
- Switching delay (adjustable) : 1...10 s
- Protection class : IP 65
- Switching voltage : max. 250 V AC | max. 115 V DC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA, 60 Watt
- Potential-free changeover contact : 1 @ 1...10 s
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
T205 VA
Stainless steel magnetic immersion probes
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : max. 2x Typ 08
- connection cable : Silikon Litze
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar (Zylinder)
- Number of contacts : max. 2 x Schließer/ Öffner wahlweise durch 180°-Drehung des Schwimmers bei 2 Schwimmern
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
- Sliding tube length : max. 1000 mm
- media density : Typ 08: 0,78 g/cm³
- float : Zylinder Edelstahl 1.4571 27 mm Ø
- min. contact distance with several floats : 50 mm
Lub-VDT USB-Kit
Software and USB kit for configuration & evaluation
Properties
- details : folgen
EK-CAN
PC program for CANopen sensors
Evaluation and configuration software for Fluid.iO CANopen sensors
Properties
- Operating system : Windows
- ltdata.BuildVersion : 1.0.5 (28.10.2025)
- installation type : ZIP, portable
- ltdata.Sprache : DE | EN
Our application engineers advise you personally, comprehensively and professionally!