Cart
TK-313 configure
EP 24V configure
BK-390 configure
T-200.L configure
ZMF-201e-IR configure
ER-214 configure
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Box : Polyethylen-Anschlusskopf (PE)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
ZMF-201e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-20X series includes sensors & transmitters for measuring gas concentrations of various gases such as CO2, methane, propane and SF-6.
This makes the sensors suitable for many applications. The ZMF-20X gas sensors are designed to be extremely rugged & suitable for use
in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Options
- Other cable lengths on request :
- ATEX certification (optional) :
Measuring ranges
- in ppm : in vol%
- 0…44.000ppm : 0…4,4 % vol (100 % LEL)
- 0…50.000ppm : 0…5 % vol
- 0…1.000.000ppm : 0…100 % vol
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
T209
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
Our application engineers advise you personally, comprehensively and professionally!