ÜTA-32 configure
ELH 24 V configure
ZS-1 configure
T200.F-24V configure
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
- Protection class : Gehäuse IP66, Stecker IP 67
- Weight : 96g
Properties TPS-420
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (dew point) : -50…+80 °C
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
- connection : G 1” (andere Gewinde auf Anfrage)
- max.length guide tube : siehe Diagramm
- Operating temperature : atmosphär. Bedingungen
- Operating pressure : atmosphär. Bedingungen
- media density : siehe Eintauchtiefe
- Number of contacts : beliebig
- Contact load : max. 10 VA, max. 230 V AC
- Length : max. 1750 mm
Material
- Sight tube : PVC transparent
- connection : PVC-Verschraubung mit PTFE-Stangenführung
- Guide rod : Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
- float : PE / PP
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
- details : folgen
ELH 24 V
Hanging electrode as leakage probe 24 V DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
Aero_aH100
Exhaust air fan with integrated dehumidification control for automatic room dehumidification
Dehumidification control, including integrated indoor and outdoor climate sensor. Controlled dehumidification takes place by comparing the indoor and outdoor climate. To support room dehumidification, a ventilation fan can be directly connected and controlled via the Aero_aH 100.
Properties
- Power supply : 230V~ 50Hz
- power consumption : 8 W
- Protection class : IPX4
- flow rate : 78 m³/h bis zu 92 m³/h
- color : verkehrsweiß, ähnlich RAL 9016
- Material : Kunststoff
- Noise level : 27 dB(A) / 32 dB(A)
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100% rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
T209-0.F
Magnetic immersion probe overfill protection for Ex zone 0 (Cat. 1)
The magnetic immersion probes T20... are used to detect fill level limit values in containers for liquid media, where an explosive atmosphere of zone 0 (cat. 1) is present in the gas space above the liquid and Ex zone 1 (cat. 2) is present outside the container, in the area of the junction box.
Properties
- connection : Polyesterdose, Aluminiumdose
- Protection class : IP 65 Dose
- Float type : Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135°C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : 6x Wechsler, 9x Schließer, 6x Öffner
- Switching current : 1A, 2A ( nur mit Schirmung)
- Switching capacity : Wechsler: 60 W/VA, Schließer: 100 W/VA Öffner: 60 W/VA
- min. contact distance with several floats : 125 mm
ZS-1
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...0,25mbar :
- 0...0,5mbar :
- 0...1mbar :
- 0...2,5mbar :
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- Weight : ca. 150g
- ltdata. :
Power supply
- nominal voltage : siehe Typenschlüssel
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
- Switching delay : siehe Typenschlüssel
- Sensitivity range : siehe Typenschlüssel
Output
- Contacts : potentialfreie Wechselkontakte
- Switching voltage(min) : 5 V
- Switching voltage (max) : 250 V AC / 150 V DC
- Overvoltage category : EN 61010-1 Kategorie III
Switching current
- Switching current : min. 5 mA
- Switching current : max. cos φ =1 5 A
- Switching current : max. cos φ = 0,7 3 A/AC
- Switching current : max. cos φ = 1
T200.F-24V
Overfill protection with 24V direct connection
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose : PO/ET-520
- ltdata.Polyethylenanschlusskopf : PE/ET-521
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24…300V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
T209
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
Our application engineers advise you personally, comprehensively and professionally!