Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
Measured variable:
:
CO2
Measuring range:
:
0…5.000 ppm
Measuring principle:
:
optisch, NDIR
Housing
:
Kunststoff
measuring grid
:
2 sec.
Accuracy
:
± 50 ppm
Protocol
:
I²C-Bus
Operating conditions Temperature
:
-0°C … 50°C
Operating conditions Humidity
:
0…85 % rH
Storage conditions Temperature
:
-30°C … 70 °C
Storage conditions Humidity
:
0…85 % rH
Properties MV-CAN
Housing
:
Plastik
Mounting
:
Hutschienenmodul für Einbau in Schaltschrank
Operating voltage
:
10…48 V
measuring grid
:
2 sec.
CAN protocol
:
CANopen 2.0 A nach CiA DS 404
Physical Layer
:
nach ISO 11898
Option
:
Bereitstellung des EDS-Files
Operating temperature
:
-40°C … +80°C
Storage temperature
:
-40°C … +120 °C
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
QFS-5x | QFS-6x
Teflon float switch for all kinds of liquids up to 150°C
The float of the QFS-50 and QFS-60 float switches is made of Teflon. Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Switching current / switching voltage
:
nur zum Anschluss an KR-163... oder andere „Namur”-Relais
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. +20°...–20°
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
Housing
:
Aluminium, eloxiert
Measuring element humidity
:
kapazitiv, betauungsfest
Measuring element temperature
:
Halbleiter
measuring resolution
:
12 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Option
:
Bereistellung des EDS-Files
tdata.
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Minimum air velocity across the sensor required for measurement
:
1,5 m/s
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
– 20…+60 °C
Storage temperature
:
– 30…+80 °C
Sensitivity
:
bei konduktiver Messung: 3, 10, 30, 100kΩ
Dimensions
:
170 x 190 x 85 mm
Weight
:
ca. 0,8 kg
Control circuits
Open circuit voltage
:
max. 10 V DC
Short-circuit current
:
max. 10 mA
Switching delay
:
ca. 0,5 s
Power supply
nominal voltage
:
230 V AC (optional 24, 115, 240 V AC 24 V DC
Nominal frequency
:
48...62 Hz
Power consumption
:
max. 3 W/VA
Output
Switching voltage
:
max. 250 V
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA | max. 50 W
Volume
:
75 dB
Lub-VDT USB-Kit
Software and USB kit for configuration & evaluation
Properties
details
:
folgen
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
NP-255
Level Switch - multiple 2...4 - pneumatic
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
Protection class EN60529
:
IP 54
connection thread
:
ab G2”
Union nut
:
ab G2¾”
Container connection flange
:
ab DN 25
Hose Ø
:
16 mm
Operating temperature
:
+60 °C
medium temperatur
:
max. +60 °C
Contact
:
Wechsler
Switching capacity
:
500 VA
Switch-on point (Viton membrane)
:
150 mm WS ±30 mm
Switch-off point (MembraneViton)
:
90 mm WS ±30 mm
Material
Pitot tube / Hose
:
PVC
Screw fitting/grommet
:
PVC
flange
:
PVC
Connection head
:
PVC
Switching voltage
silver
:
max. 250 V AC
Gold
:
max. 24 V AC
Switching current
silver
:
max. 6 A
Gold
:
max. 100 mA
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
connection
:
Edelstahl (1.4571)
Protection class
:
IP 65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
connection thread
:
G1", G1¼", G1½”
Coating length
:
voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
Rod diameter
:
4 oder 6 mm
rod length
:
max. 6 m
Operating pressure media side
:
max. 40 bar
Maximum permissible electrical connection values
:
Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
Connection values
:
Ui 15V | Li 10 mA | Pi 100 mW
Internal inductances / capacitances
:
vernachlässigbar klein
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
Medien & Umgebung 80 °C
Category 2 Class T5
:
Medien & Umgebung 95°C
Category 2 Class T4
:
Medien 130°C, Umgebung 100°C
Category 2 Class T3...T1
:
Medien 150°C, Umgebung 100 °C
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W