Cart
product added to request
T-200.L 24V configure
OAA-300 configure
HD-110 | HD-112 | HD-114 configure
EF 3…5 24 V configure
TK-303 configure
T-200.L 24V
Leakage probes with general building authority approval
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Head : Polyethylenanschlusskopf (PE)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24...30 V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : – 20…+60 °C
- Storage temperature : – 30…+80 °C
- Sensitivity : bei konduktiver Messung: 3, 10, 30, 100kΩ
- Dimensions : 170 x 190 x 85 mm
- Weight : ca. 0,8 kg
Control circuits
- Open circuit voltage : max. 10 V DC
- Short-circuit current : max. 10 mA
- Switching delay : ca. 0,5 s
Power supply
- nominal voltage : 230 V AC (optional 24, 115, 240 V AC 24 V DC
- Nominal frequency : 48...62 Hz
- Power consumption : max. 3 W/VA
Output
- Switching voltage : max. 250 V
- Switching current : max. 3 A
- Switching capacity : max. 500 VA | max. 50 W
- Volume : 75 dB
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
- Housing : Kunststoffgehäuse*
- Dimensions (LxBxH) : 18 x 90 x 62 mm
- Internal circuits : Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
- Fieldbus and I/O level : getrennt durch galvanische Trennung
- ltdata.*zumAufrastenaufDIN-Trageschienen :
ElectricalConnection
- Operating voltage : 11...32V DC (typ. 24V DC)
- Operating temperature : 0...+55 °C
- Operating temperature : optional -40...+70 °C
- Conductor cross-section : 0,08...1,5 mm² (AWG28...AWG14)
CAN bus properties
- baud rate (max.) : 1 MBit
- ciA Standards : Ds301 Version 4.2 & DS401 Version 3.0
- ISO standards : ISO11898 (+ Transceiver TJA1050)
- PDO : siehe Dokumente
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- connection : integrierter Anschlusskopf
- Protection class : IP 65
- connection thread : G 1¼"
- Material Screw connection : PPH
- Material electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- material coating : PTFE
- Coating length : voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
- Rod diameter : 4 mm, 6 mm
- rod length : max. 6 m
- Operating temperature : 85 °C
- Operating pressure : atmosphärisch
- Spacer : ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24 V DC ± 15%
- Power consumption : max. 2 W (Klemme A1, A2)
- Switching voltage : max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
- Switching current : max. 3 A AC, 3 A DC min. 1 mA
- Switching capacity : max. 750 VA, 150 W
- Sensitivity : 3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
Our application engineers advise you personally, comprehensively and professionally!