Ex-QFS-30
:
waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
Ex-QFS-31
:
waagerecht mit Flansch ab DN 100 (PP)
CS-11
CO2 Sensor with digital Interface
Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
Measured variable:
:
CO2
Measuring range:
:
0…5.000 ppm
Measuring principle:
:
optisch, NDIR
Housing
:
Kunststoff
measuring grid
:
2 sec.
Accuracy
:
± 50 ppm
Protocol
:
I²C-Bus
Operating conditions Temperature
:
-0°C … 50°C
Operating conditions Humidity
:
0…85 % rH
Storage conditions Temperature
:
-30°C … 70 °C
Storage conditions Humidity
:
0…85 % rH
Properties MV-CAN
Housing
:
Plastik
Mounting
:
Hutschienenmodul für Einbau in Schaltschrank
Operating voltage
:
10…48 V
measuring grid
:
2 sec.
CAN protocol
:
CANopen 2.0 A nach CiA DS 404
Physical Layer
:
nach ISO 11898
Option
:
Bereitstellung des EDS-Files
Operating temperature
:
-40°C … +80°C
Storage temperature
:
-40°C … +120 °C
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80°C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24…230 V AC/DC
Power consumption
:
≤ 2 W
Output
Output contact
:
2 potentialfreie Wechselkontakte
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 5 A AC / 5 A DC
Switching capacity
:
max. 750 VA / 90 W
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
CE marking
:
siehe Konformitätserklärung
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
Our application engineers advise you
personally, comprehensively and professionally!