Cart
XR-6x0 | XR-6x1 configure
GSB-390 configure
W-35X configure
EP 24V configure
QFS-5x | QFS-6x configure
ELH 24 V configure
EF2X configure
BK-390 configure
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
- Quiescent current : umschaltbar
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
GSB-390
Glass float with magnet insert
for actuating monostable and bistable contacts
Variants
- 150 : AußenØ 26,5 x 150 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 50 g
- 190 : AußenØ 26,5 x 190 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 61 g
- 205 : AußenØ 26,5 x 205 mm (3 Magnete auch für bistabile Kontakte) Gewicht ca. 69 g
W-35X
Water Level Gauge with sight glass indicator
The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
- Tank connection : Flansch ab DN 25 oder Verschraubung ab G ½"
- Material Float : PPH max. 2,5 bar, Glas max. 10 bar
- cable length : bei monostabilem Kontakt: Standard 2 m
- Number of contacts : beliebig
- Contact distance : min. 10 mm
- Temperature of the fluid : mit Plexiglasrohr max. +70 °C
- media density : ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
- Material tube sight glass : transparentes PVC
- Temperature of the fluid : max. +60 °C
- Operating pressure : max. 2,5 bar
- Material flange : PVC
- Material connection with angle valve : PVC
- Material sealing ring : Gummi
Properties W-351
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Rotguss
- Material connection with angle valve : Rotguss
- Material sealing ring : Silikon
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-352
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4571 als Bogen 90°
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-353
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4401
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
QFS-5x | QFS-6x
Teflon float switch for all kinds of liquids up to 150°C
The float of the QFS-50 and QFS-60 float switches is made of Teflon. Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Operating temperature : max. +150°C
- Operating pressure : 1 bar
- media density : ρ ³ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
ELH 24 V
Hanging electrode as leakage probe 24 V DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
EF2X
Double pipe and filling pipe monitoring
EF2L and EF2T -conductive-
with general technical approval for construction Z-65.13-405
Properties
- ltdata.Elektr.Anschluss : Stecker GDM
- Protection class EN60529 : IP 65 mit Dichtung
- connection : PVC Überwurfmutter G 1 ¼“
- ltdata.BetriebstemperaturPVC : max. +60 °C
- ltdata.BetriebstemperaturPE : max. +80 °C
- Storage temperature : -30...+85 °C
- Operating pressure : max. 6 bar
Material
- Pipe : PVC | PE
- Sensor rods : Edelstahl 1.4571 | Hastelloy B/C | Titan | Tantal
tdata.ElektronikteilET-473L|ET-473T
- nominal voltage : 20...30 V DC
- Power consumption : 1 VA
- Output contact : Schließer | Öffnerkontakt (NO/NC) (nicht potentialfrei)
- Switching voltage : 12...30 V DC
- Switching current : max. 300 mA
- Switching capacity : max. 9 W
- Sensitivity range : 2...30 kOhm
- ltdata. :
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!