Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
connection thread
:
G 1/2” Standard | G 3/4” | G1”
Cable
:
TPK (Standard) | SIL (Silikon) | FEP (Teflon)
rod length
:
max. 6.000 mm
Operating pressure
:
max. 40 bar
Material
electrode body
:
Edelstahl 1.4571
Process connection
:
Edelstahl 1.4571
Coating
:
PTFE
electrode rod
:
Edelstahl 1.4571
on request
:
Hastelloy C | Tantal
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
Housing
:
Kunststoff
Power supply 24V
:
24V DC | 230V
Measuring element and parameter
Measuring principle
:
optisch, NDIR
measuring grid
:
2 sec.
Accuracy
:
± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
Our application engineers advise you