Ex-QFS-3x
Mercury-free float switches with Ex approval
These float switches have a mercury-free switching system consisting of a microswitch and a ball which actuates this switch.
Technical Data
- Protection class EN60529 : IP 68
- Material Float : PP
- Cable : TPK (PVC Basis), PVC Basis verstärkt, Polyurethan, Silikon, Teflon, Ethylen-Acrylat-Kautschuk
- Conductor cross-section : 3x 0,75 mm², Polyurethan 3x 0,5 mm²
- Operating temperature TPK(V) : AEM Kabel max.+ 60 °C
- Operating temperature PUR cable : max.+ 70 °C
- Operating temperature SIL, FEP cable : max.+ 85 °C
- Operating pressure : max. 1 bar Zylinder| max. 2 bar Kugel
- Switching system : Mikroschalter
- Contact type : Wechsler, NO, NC
- Electrical connection data, Ex-protection : siehe EG-Prüfbescheinigung TüV 09 ATEX 555342
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- CE marking : siehe Konformitätserklärung
- Weight : ca. 200 g
Media density Ex-QFS-30
- TPK(V) cable : ρρ 0,85 g/cm³
- PUR cable : ρρ 0,95 g/cm³
- SIL cable : ρρ 0,90 g/cm³
- FEP cable : ρρ 0,95 g/cm³
- AEM Cable : ρρ 0,90 g/cm³
Media density Ex-QFS-31
- Sphere : ρρ 0,60 g/cm
Mounting position
- Ex-QFS-30 : waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
- Ex-QFS-31 : waagerecht mit Flansch ab DN 100 (PP)
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
- Dimensions : 180 x 48 x 36,5 mm ( L x B x H )
- Weight : ca. 1,5 kg
- Protection class : IP68
- Cable length (standard) : 15 m
- Bending radius : > 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
- Temperature range : 0°C ... 50°C
- Mounting shoe material : V2A 1,5mm
Certificates
- EX / ATEX : IBExU 04 ATEX 1256
Measuring principle
- Flow velocity: Ultrasonic Doppler :
- Filling level: Differential pressure :
Flow velocity
- Measuring range : 0,01 - 4 m / s
- Measuring accuracy : +/- 5 % vom Momentanwert im Kanal
- Temperature drift : 0,1% / °C ( Meßspanne )
- Temperature drift : 0,05% / °C ( Nullpunkt )
- Output signal : 4 - 20 mA
Filling level
- Measuring ranges : 0 –1 m ; 0 – 2 m ; 0 – 4 m
- Measuring accuracy : < 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
- Temperature drift : 0,005% / °C v.E. Meßspanne
- Temperature drift : 0,005% / °C v.E. Nullpunkt
- Material : Al2O3 (96%) aktive Fläche
- Output signal : 4 – 20 mA
- Zero point : norm 4 mA ( +/- 3 % )
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
HE
Pendant electrodes – single, multiple
suitable for high tanks, wells and sewers
tdata.AnschlussmitDose
- Protection class EN60529 : IP 54
- connection thread : G 2”
tdata.AnschlussohneDose
- Protection class EN60529 : IP 67
- connection thread : n.a. / G 2”
Material
- electrode body : PVC, PTFE, PPH
- Screw connection : PVC, PTFE
- Cable : PVC, PTFE
- electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
Operating temperature
- ltdata.HE-PVC : 60 °C
- ltdata.HE-PTFE : 150°C
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80°C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties TPS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…100% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -50...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
T209-0
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : PO-Dose oder AA-Dose
- Protection class : IP 65 Dose
- Float type : max. 6x Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- Number of contacts : max. 7x Wechsler / max. 10x Schließer / 7x Öffner
- Switching current : 1A, 2A
- Switching capacity : Wechsler 60W/VA | Schließer 100 W/VA | Öffner 60 W/VA
- min. contact distance with several floats : 125 mm
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
Our application engineers advise you personally, comprehensively and professionally!