Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
connection thread
:
G 1/2” Standard | G 3/4” | G1”
Cable
:
TPK (Standard) | SIL (Silikon) | FEP (Teflon)
rod length
:
max. 6.000 mm
Operating pressure
:
max. 40 bar
Material
electrode body
:
Edelstahl 1.4571
Process connection
:
Edelstahl 1.4571
Coating
:
PTFE
electrode rod
:
Edelstahl 1.4571
on request
:
Hastelloy C | Tantal
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80°C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24…230 V AC/DC
Power consumption
:
≤ 2 W
Output
Output contact
:
2 potentialfreie Wechselkontakte
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 5 A AC / 5 A DC
Switching capacity
:
max. 750 VA / 90 W
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
CE marking
:
siehe Konformitätserklärung
Our application engineers advise you