Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
T204.F
with general building authority approval Z-65.11-404
Properties
connection
:
Polyester Dose | Aluminium Dose
Protection class
:
IP 65 Dose
number of floats
:
max. 4x
Operating temperature
:
max. 135 °C
F-Contact
:
1 / 12 kΩ
Number of additional contacts
:
max. 3x Wechsler | 5x Schließer | 3x Öffner
Stainless steel ball 61 mm Ø
:
max. 20 bar | 0,65 g/cm³
Stainless steel cylinder 44 mm Ø
:
max. 15 bar | 0,76 g/cm³
min. contact gap type 03
:
75 mm
min. contact gap type 04
:
85 mm
min. contact gap type 09
:
75 mm
Switching contacts and switching capacity
Changeover contact
:
max. 3x | 60W/VA
normally open
:
max. 5x | 100 W / VA
Normally closed contact
:
max. 3x | 60 W/VA
NP-256
Level Switch - multiple 2...4 - pneumatic (hose)
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
Protection class EN60529
:
IP 54
connection thread
:
ab G2”
Union nut
:
ab G2¾”
Container connection flange
:
ab DN 25
HoseØ
:
13x2 mm
Operating temperature
:
+60 °C
medium temperatur
:
max. +60 °C
Contact
:
Wechsler
Switching capacity
:
500 VA
Switch-on point (Viton membrane)
:
150 mm WS ±30 mm
Switch-off point (MembraneViton)
:
90 mm WS ±30 mm
Material
Hose
:
PVC
Screw fitting/grommet
:
PVC
flange
:
PVC
Connection head
:
PVC
Switching voltage
silver
:
max. 250 V AC
Gold
:
max. 24 V AC
Switching current
silver
:
max. 6 A
Gold
:
max. 100 mA
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
Pressure range
:
0...500mbar gestuft
supply
:
12 - 24 V DC
Output
:
Relais 230 V/1A
overload
:
2 x Messbereich
Med. connection
:
Schlauch
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
KS-17
digital climate transmitter
The digital climate sensor measures temperature and relative humidity in a combined sensor element.
Technical specifications
Housing
:
Plastik
Measured variable
:
Temperatur und relative Feuchte kapazitiv (alle Geräte)
Measurable temperature
:
-40…+120 °C
Measuring range humidity
:
0…100 % rH
Sensor technology
:
Halbleiter
Power supply
:
2,4…5,5 V
Output
:
digitales Protokoll
features
:
Gehäuse für Oberflächenmontage
Our application engineers advise you
personally, comprehensively and professionally!