Cart
product added to request
EFV2 20…230V configure
ZT-F configure
TSR-CAN-03
CANopen transmitter for temperature measurement in media
High-quality stainless steel transmitter for precise temperature measurement in all stainless steel-compatible media
Measurement parameters
- Measuring range : -40…+80 °C (optional +150°C)
- deviation : ± 0,3 K (-40…+80 °C)
- Measuring element : Halbleiter
- measuring resolution : 10 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 12…27 V ±20 %
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
EFV2 20…230V
Conductive electrodes with 24...230 V direct connection
The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾" | S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Kohlestifte
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Adjustable sensitivity range : 2..100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Power supply
- nominal voltage : 24...230 V AC/DC
- Power consumption : ≤ 2 W
Output
- potential-free changeover contacts : 2
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs- LED grün Funktions-LED rot
- Switching delay : ca. 0,5 s
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
CS-11
CO2 Sensor with digital Interface
Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
- Measured variable: : CO2
- Measuring range: : 0…5.000 ppm
- Measuring principle: : optisch, NDIR
- Housing : Kunststoff
- measuring grid : 2 sec.
- Accuracy : ± 50 ppm
- Protocol : I²C-Bus
- Operating conditions Temperature : -0°C … 50°C
- Operating conditions Humidity : 0…85 % rH
- Storage conditions Temperature : -30°C … 70 °C
- Storage conditions Humidity : 0…85 % rH
Properties MV-CAN
- Housing : Plastik
- Mounting : Hutschienenmodul für Einbau in Schaltschrank
- Operating voltage : 10…48 V
- measuring grid : 2 sec.
- CAN protocol : CANopen 2.0 A nach CiA DS 404
- Physical Layer : nach ISO 11898
- Option : Bereitstellung des EDS-Files
- Operating temperature : -40°C … +80°C
- Storage temperature : -40°C … +120 °C