Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
properties KG-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
properties KG-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
Dimensions (LxBxH in mm)
:
30 x 45,4 x 97,3
Protection type/class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
QFS-1X
Float switch with reed switch (mercury-free)
Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Properties
Protection class EN60529
:
IP 68
Cable entry
:
PVC , PTFE
Conductor cross-section
:
3 x 0,75 mm², PUR 3x0,5mm²
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC (QFS-11 nur NO oder NC)
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Float
Material Float
:
PE (Polyethylen)
ltdata.
:
ltdata.
:
ltdata.
:
Operating temperature
TPK(V), AEM
:
max. + 60 °C
PUR
:
max. + 70 °C
Silicone,Tefloncable with PE float
:
max. + 80 °C
Operating pressure
Cylinder
:
max. 1 bar
Sphere
:
max. 2 bar
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
BI
Bistable Switch
Properties
Protection class
:
IP 65
Switching current
:
max. 1 A
Switching voltage
:
max. 24 V
Switching capacity
:
max. 20 W/VA
Material
Housing
:
Messingrohr Ø 10 x 1
Cable
:
TPK (PVC basis) | SIL (Silikon)
Operating temperature
TPK
:
–15 ° ... + 60 °C
SIL
:
–15 ° ... +130 °C
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
Our application engineers advise you