Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
NSP-X-E
Vibrating Limit Switch
The vibrating limit switch is a level limit switch for all kinds of fluids and is used in tanks, containers and pipelines.
Properties
Protection class EN60529
:
IP 65/IP 67
Operating pressure
:
≤ 40 bar
media density
:
ρ ≥ 0,7 g/cm³
Viscosity
:
max. 10000 mm²s
Rated current
:
< 15 mA
Protection class
:
III
Output
:
PNP
power
:
kurzschlussfest, überlastsicher
Display
:
LED (grün, rot)
Switching delay (cover)
:
ca. 0,5 s
Switching delay (release)
:
ca. 1 s
NSP-1-E
connection thread
:
G 1”
Operating temperature
:
–40...+150 °C
Storage temperature
:
–40...+85 °C
nominal voltage
:
10...55 V DC (verpolsicher)
Current output
:
≤ 350 mA
NSP-2-E
connection thread
:
G ½”
Operating temperature
:
–40...+100 °C
Storage temperature
:
–20...+70 °C
nominal voltage
:
10...35 V DC (verpolsicher)
Current output
:
≤ 250 mA
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
Material
:
1.4571 / 1.4404 (316Ti / 316L)
Protection class
:
IP65
Process temperature
:
-10°C … +130°C | (integriertes Pt100 im Messfühler)
max. process pressure
:
Vakuum ... 64 bar
Process connections
:
NPT | M48 | Varivent® | Tri-Clamp
Cable length sensor - transmitter
:
Max. 1.000 Meter
max. flow velocity
:
5 m / sec
Ex approval
:
II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
Sphere
:
VA-100B
Cylinder
:
VA-100C
Repeatability
VA-100B
:
± 0,5% | ± 1 Digit
VA-100C
:
± 0,3% | ±1 Digit
Measuring ranges
VA-100B
:
0,1 - 2.500 mPa·s x g/cm³
VA-100C
:
10 - 25.000 mPa·s x g/cm³
Probe dimensions
VA-100B
:
Ø 32 x 145 mm
VA-100C
:
Ø 32 x 120 mm
installation positions
Reservoir
:
tanks
:
Pipe
:
flow cell
:
Installation is position-independent
:
Our application engineers advise you