Cart
product added to request
Ex-QFS-3x configure
TK-312 configure
ES-22 configure
NP-256 configure
KS-CAN-03 configure
Ex-QFS-3x
Mercury-free float switches with Ex approval
These float switches have a mercury-free switching system consisting of a microswitch and a ball which actuates this switch.
Technical Data
- Protection class EN60529 : IP 68
- Material Float : PP
- Cable : TPK (PVC Basis), PVC Basis verstärkt, Polyurethan, Silikon, Teflon, Ethylen-Acrylat-Kautschuk
- Conductor cross-section : 3x 0,75 mm², Polyurethan 3x 0,5 mm²
- Operating temperature TPK(V) : AEM Kabel max.+ 60 °C
- Operating temperature PUR cable : max.+ 70 °C
- Operating temperature SIL, FEP cable : max.+ 85 °C
- Operating pressure : max. 1 bar Zylinder| max. 2 bar Kugel
- Switching system : Mikroschalter
- Contact type : Wechsler, NO, NC
- Electrical connection data, Ex-protection : siehe EG-Prüfbescheinigung TüV 09 ATEX 555342
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- CE marking : siehe Konformitätserklärung
- Weight : ca. 200 g
Media density Ex-QFS-30
- TPK(V) cable : ρρ 0,85 g/cm³
- PUR cable : ρρ 0,95 g/cm³
- SIL cable : ρρ 0,90 g/cm³
- FEP cable : ρρ 0,95 g/cm³
- AEM Cable : ρρ 0,90 g/cm³
Media density Ex-QFS-31
- Sphere : ρρ 0,60 g/cm
Mounting position
- Ex-QFS-30 : waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
- Ex-QFS-31 : waagerecht mit Flansch ab DN 100 (PP)
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA, 2W
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0-4...10 kW
Output
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Current output : 0/4... 20 mA bezogen auf die Masse des Eingangs
- Voltage output : 0/2... 10 V
- Mounting : Tragschiene nach EN 50022
- Weight : 175 g
ES-22
electronic safety pressure limiter with 2 safety functions
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
NP-256
Level Switch - multiple 2...4 - pneumatic (hose)
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
- Protection class EN60529 : IP 54
- connection thread : ab G2”
- Union nut : ab G2¾”
- Container connection flange : ab DN 25
- HoseØ : 13x2 mm
- Operating temperature : +60 °C
- medium temperatur : max. +60 °C
- Contact : Wechsler
- Switching capacity : 500 VA
- Switch-on point (Viton membrane) : 150 mm WS ±30 mm
- Switch-off point (MembraneViton) : 90 mm WS ±30 mm
Material
- Hose : PVC
- Screw fitting/grommet : PVC
- flange : PVC
- Connection head : PVC
Switching voltage
- silver : max. 250 V AC
- Gold : max. 24 V AC
Switching current
- silver : max. 6 A
- Gold : max. 100 mA
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
- Housing : Aluminium, eloxiert
- Measuring element humidity : kapazitiv, betauungsfest
- Measuring element temperature : Halbleiter
- measuring resolution : 12 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Option : Bereistellung des EDS-Files
tdata.
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Minimum air velocity across the sensor required for measurement : 1,5 m/s
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!