The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
Housing
:
Kunststoff
Protection class
:
IP00
Ambient temperature
:
-20…+60°C
Supply voltage
:
24V DC +20% / -10%
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
Protection class EN60529
:
IP68
Side installation
:
PVC-Stopfbuchsverschraubung G 2”
Installation from above
:
PVC-Stopfbuchsverschraubung G 2”
Operating pressure
:
max. 2 bar
Contact
:
Wechselkontakt
Switching voltage
:
4....250 V AC / DC
Switching current
:
1mA.....1A
Switching capacity
:
60W/VA
media density
:
ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
Material Float
:
Polyethylen
Cable
TPK
:
PVC Basis
TPKV
:
PVC Basis verstärkt
PUR
:
Polyurethan
NEO
:
Neopren
SIL
:
Silikon
FEP
:
Teflon
AEM
:
Ethylen-Acrylat-Kautschuk
Operating temperature
TPK(V), NEO, AEM
:
max.+60 °C
PUR
:
max.+70 °C
FEP, SIL
:
max.+80 °C
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
Housing
:
Aluminium, eloxiert
Measuring element humidity
:
kapazitiv, betauungsfest
Measuring element temperature
:
Halbleiter
measuring resolution
:
12 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Option
:
Bereistellung des EDS-Files
tdata.
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Minimum air velocity across the sensor required for measurement
:
1,5 m/s
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm