The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
Housing
:
Kunststoff
Protection class
:
IP00
Ambient temperature
:
-20…+60°C
Supply voltage
:
24V DC +20% / -10%
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
-10...70 °C
Storage temperature
:
-25...70 °C
Power supply
:
15...30 V DC
power
:
max. 25 mA
Output
:
2-Leiter-Technik | 4...20 mA
Measuring range
:
0,8...10 mWs (Standard)
Overpressure
:
ca. 20 %
Deviation from characteristic curve
:
Nichtlinearität,
Insulation resistance
:
> 100 kΩ
Short-circuit resistance
:
permanent
Reverse polarity protection
:
keine Schädigung o. Funktion bei vertauschten Anschlüssen
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
connection
:
Flansch ab DN 15
Material
:
rostfreier Edelstahl, PVC, PPH, PVDF
Material flange
:
Edelstahl 1.4571, C22.8
Material Float
:
Edelstahl, Titan, PVC, PPH, PVDF
Number of contacts
:
beliebig
Contact load
:
max 10 VA, max 230 V AC
Display length
:
max. 6m
Operating temperature
PTFE seal
:
max. 150 °C
Stainless steel: Klingerit seal
:
max. 200 °C
PVC
:
max. 60 °C
PPH
:
max. 90 °C
PVDF
:
max. 130 °C
Stainless steel float
Weight
:
~ 300 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
16 bar
media density
:
ρ ≥ 0,70 g/cm³
Stainless steel float
Weight
:
~ 320 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
40 bar
media density
:
ρ ≥ 0,75 g/cm³
Titanium float
Weight
:
~ 180 g
Dimensions
:
Ø 52 x 150
Operating pressure
:
16 / 40 bar
media density
:
ρ ≥ 0,73 g/cm³
PVC float
Weight
:
~ 331 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,8 g/cm³
PPH float
Weight
:
~ 283 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,69 g/cm³
PVDF float
Weight
:
~ 352 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,85 g/cm³
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
KS-17
digital climate transmitter
The digital climate sensor measures temperature and relative humidity in a combined sensor element.
Technical specifications
Housing
:
Plastik
Measured variable
:
Temperatur und relative Feuchte kapazitiv (alle Geräte)
Measurable temperature
:
-40…+120 °C
Measuring range humidity
:
0…100 % rH
Sensor technology
:
Halbleiter
Power supply
:
2,4…5,5 V
Output
:
digitales Protokoll
features
:
Gehäuse für Oberflächenmontage
EK-CAN
PC program for CANopen sensors
Evaluation and configuration software for Fluid.iO CANopen sensors
Properties
ltdata.Betriebssystem
:
tba.
ltdata.freierFestplattenspeicher
:
tba.
ltdata.Bildschirmauflösung
:
tba.
ltdata.Softwarearchitektur
:
tba.
ltdata.Softwaretyp
:
tba.
ltdata.Installationsart
:
tba.
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.