Cart
Ex-BK configure
KS-CAN-03 configure
QFS-40 configure
LU-180 EX configure
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –20...+120 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
- Dimensions : 80 mm x 75 mm x 57 mm
Material
- Housing : Aluminium
- Mounting clip : V2A
- Rivet : V2A
- Screw connection : M 20 x 1.5, V2A
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 24...250 V AC/DC
- Switching current : 20 mA...6 A AC/DC
- Switching capacity(min.) : max. 500 VA, 60 W
- Switching capacity(max.) : min. 2 VA/W
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
- Housing : Aluminium, eloxiert
- Measuring element humidity : kapazitiv, betauungsfest
- Measuring element temperature : Halbleiter
- measuring resolution : 12 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Option : Bereistellung des EDS-Files
tdata.
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Minimum air velocity across the sensor required for measurement : 1,5 m/s
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
- Switch housing : PPH| PVDF
- Seal : NBR (PPH) | FPM (PVDF)
- Operating temperature : PPH max. 80 °C| PVDF max. 100 °C
- Operating pressure : max. 10 bar
- Mounting position : horizontal (±30° von der Horizontalen)
- Contact assembly : Schliesser-, Öffnerkontakt (je nach Einbau)
- Electrical connection : PVC-Kabel
- Switching capacity : max. 230 V AC/DC| max. 40 VA, max. 2 A
- Contact resistance : max. 80 mW
- Min. electric strength : 400 V DC / 1 s
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- fluid density : PPH > 0,6 kg/dm³ | PVDF > 0,95 kg/dm³
- Protection class : IP 68
Connections
- external installation : G ½"
- internal installation : M16
TSR-CAN-03
CANopen transmitter for temperature measurement in media
High-quality stainless steel transmitter for precise temperature measurement in all stainless steel-compatible media
Measurement parameters
- Measuring range : -40…+80 °C (optional +150°C)
- deviation : ± 0,3 K (-40…+80 °C)
- Measuring element : Halbleiter
- measuring resolution : 10 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 12…27 V ±20 %
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
T200
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
LU-180 EX
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!